M’Ax User Guide
105
Issue Number: 4
Example
1.
Set
4.53
Symmetrical current limit after motor thermal-overload
alarm at
200
(the largest of the symmetrical current limit values).
2.
Set
4.54
Thermal-overload time to trip at
12
(process cycle time,
rounded-up to nearest integer).
3.
Calculate the following:
4.
Calculate the following:
5.
Calculate the following:
6.
Enter the calculated value into
4.52
.
7.
Perform the following, as appropriate:
Version _AN
Initiate the save operation by setting parameter
XX.00
at
1000
.
Execute the operation by performing either of the following:
•
While the display is in Edit mode, press at the same time:
•
Set parameter
10.38
at
100
(via serial communications)
Version _SL
Version _AN
(if required)
Ensure the Drive is disabled by checking that the
Hardware enable
contact is open or that parameter
6.15
is set at
0
, then perform either
of the following:
•
Initiate the store operation by setting parameter
0.50
at
2
(
Prog
).
Execute the operation by setting parameter
10.38
at
100
.
Set
11.67
Flash update enable at
1
.
Parameter
Value
4.15
Motor – thermal time-constant
89
4.07
Symmetrical current limit Kc1
150
4.24
Symmetrical current limit Kc2
200
4.28
Symmetrical current limit Kc3
175
Process cycle time
11.5s
Gain sequencing using all three PID-gains buffers
t
c
4.15
[
]
–
In 1
2
105
2
4.53
[
]
-------------------
–
è
ø
ç
÷
æ
ö
×
=
t
c
89
–
In 1
2
105
2
200
------------
–
è
ø
ç
÷
æ
ö
×
28.7 s
( )
=
=
t
D
t
C
4.54
[
]
–
28.7
12
–
16.7 s
( )
=
=
=
4.52
[
]
4.53
[
]
1
e
t
–
D
4.15
[
]
⁄
–
×
=
4.52
[
]
200
[
]
1
e
16.7
–
(
)
89
⁄
–
×
82.7
=
=
(%)