4. Functions
AD12-8(PM)
57
Output data
Set the data to output as an analog signal. You can use a software command to output from a single
channel or from multiple channels (a specified number of channels starting from channel 0).
The formula below gives the relationship between the output data and voltage on the AD12-8(PM).
Output data = (Voltage x 4096)
÷
4.096
The table below lists the output voltage for different output data values.
Voltage
Output data(12-bit)
+4.095V
4095
:
:
+20.49V
2049
+2.048V
2048
+2.047V
2047
:
:
+0.0000V
0
Ex.: When 3V is output at a resolution of 12-bit.
Output data
=
3
×
4096 ÷ 4.096
=
3000
Содержание AD12-8(PM)
Страница 1: ...PC HELPER Analog I O PC Card AD12 8 PM User s Guide CONTEC CO LTD ...
Страница 7: ...vi AD12 8 PM ...
Страница 15: ...1 Before Using the Product 8 AD12 8 PM ...
Страница 45: ...2 Setup 38 AD12 8 PM ...
Страница 67: ...4 Functions 60 AD12 8 PM ...
Страница 77: ...5 About Software 70 AD12 8 PM ...