Cat6A Specifications and Testing Requirements
C
AT
6A S
PECIFICATIONS
AND
T
ESTING
R
EQUIREMENTS
Cat6A connections must be tested with a device that can measure the cable parameters against the thresholds
defined in ANSI/TIA standards (such as the Fluke DTX-1800 and DSX-5000).
shows the end-to-end
channel from the CAN/TEN to the CAP L, which is inclusive of the Cat6A cable, the Cat6A Patch Cord, and the
Panel and connection box. The end-to-end channel must meet the Cat6A U/UTP performance defined by the
TIA/EIA 568 C.2 standard; see
Figure 18.
ERA End-to-End Channel
Some cables list their performance in “typical” performance values. However, sweep-testing is necessary
to confirm actual performance. CommScope strongly recommends using Cat6A cable that has been tested
to the listed frequency with test confirmation available for inspection.
Table 15.
Cat6A U/UTP Performance Standards (TIA/EIA 568 C.2)
MHz Insertion Loss (dB)
Channel/Link
NEXT (dB)
Channel/Link
PSum NEXT (dB)
Channel/Link
ACRF (dB)
Channel/Link
PSum ACRF (dB)
Channel/Link
Return Loss
(dB) Channel/Link
1
2.3/1.9
65.0/65.0
62.0/62.0
63.3/64.2
60.3/61.2
19.0/19.1
4
4.2/3.5
63.0/64.1
60.5/61.8
51.2/52.1
48.2/49.1
19.0/21.0
8
5.8/5.0
58.2/59.4
55.6/57.0
45.2/46.1
42.2/43.1
19.0/21.0
10
6.5/5.5
56.6/57.8
54.0/55.5
43.3/44.2
40.3/41.2
19.0/21.0
16
8.2/7.0
53.2/54.6
50.6/52.2
39.2/40.1
36.2/37.1
18.0/20.0
20
9.2/7.8
51.6/53.1
49.0/50.7
37.2/38.2
34.2/35.2
17.5/19.5
25
10.2/8.8
50.0/51.5
47.3/49.1
35.3/36.2
32.3/33.2
17.0/19.0
31.25
11.5/9.8
48.4/50.0
45.7/47.5
33.4/34.3
30.4/31.3
16.5/18.5
62.5
16.4/14.1
43.4/45.1
40.6/42.7
27.3/28.3
24.3/25.3
14.0/16.0
100
20.9/18.0
39.9/41.8
37.1/39.3
23.3/24.2
20.3/21.2
12.0/14.0
200
30.1/26.1
34.8/36.9
31.9/34.3
17.2/18.2
14.2/15.2
9.0/11.0
250
33.9/29.5
33.1/35.3
30.2/32.7
15.3/16.2
12.3/13.2
8.0/10.0
300
37.4/32.7
31.7/34.0
28.8/31.4
13.7/14.6
10.7/11.6
7.2/9.2
400
43.7/38.5
28.7/29.9
25.8/27.1
11.2/12.1
8.2/9.1
6.0/8.0
500
49.3/43.8
26.1/26.7
23.2/23.8
9.3/10.2
6.3/7.2
6.0/8.0
Propagation Delay is 555 nanoseconds for channel/498 nanoseconds for link tested at 10 MHz.
Delay Skew is 50 nanoseconds for channel/44 nanoseconds for link tested at 10 MHz.
For additional information, see also
CommScope Product Specifications for the GigaSPEED X10D® 2091B
ETL Verified Category 6A U/UTP Cable
(760107201 | 2091B BL 4/23 W1000). (Click
document online.)
Cat6A
Patch
Cord
Cat6A Cable
Modular
Panel
Connecon
Box
CAT/TEN
CAP L
Cat6A
Patch
Cord
Содержание e-POI
Страница 1: ...CommScope ERA WCS and e POI Subracks and Power Supply Unit Installation Guide M0201ABK_uc June 2021 ...
Страница 85: ......
Страница 86: ......