507716-01
Page 20 of 58
Issue 1717
GUH95C Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 0 - 4,500 ft
Number
of 90°
Elbows
Used
2nd Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
70
90
110
135
045
70
90
110
135
045
70
90
110
115
1
68
53
37
17
n/a
100
85
59
34
n/a
116
116
109
109
100
2
63
48
32
12
95
80
54
29
111
111
104
104
95
3
58
43
27
7
90
75
49
24
106
106
99
99
90
4
53
38
22
n/a
85
70
44
19
101
101
94
94
85
5
48
33
17
80
65
39
14
96
96
89
89
80
6
43
28
12
75
60
34
n/a
91
91
84
84
75
7
38
23
7
70
55
29
86
86
79
79
70
8
33
18
n/a
65
50
24
81
81
74
74
65
9
28
13
60
45
19
76
76
69
69
60
10
23
8
55
40
14
71
71
64
64
55
Concentric Termination Elevation 4500 - 10,000 ft
Number
of 90°
Elbows
Used
2nd Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
70
90
110
135
045
70
90
110
135
045
70
90
110
135
1
68
53
37
n/a
n/a
100
85
59
34
n/a
116
116
109
109
100
2
63
48
32
95
80
54
29
111
111
104
104
95
3
58
43
27
90
75
49
24
106
106
99
99
90
4
53
38
22
85
70
44
19
101
101
94
94
85
5
48
33
17
80
65
39
14
96
96
89
89
80
6
43
28
12
75
60
34
n/a
91
91
84
84
75
7
38
23
7
70
55
29
86
86
79
79
70
8
33
18
n/a
65
50
24
81
81
74
74
65
9
28
13
60
45
19
76
76
69
69
60
10
23
8
55
40
14
71
71
64
64
55
*Size intake and exhaust pipe length separately. Values in table are for intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Table 5B.
Содержание GUH95C
Страница 3: ...507716 01 Page 3 of 58 Issue 1717 Figure 1 Parts Arrangement...
Страница 22: ...507716 01 Page 22 of 58 Issue 1717 Figure 25 Figure 26...
Страница 37: ...507716 01 Page 37 of 58 Issue 1717 Figure 59 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...
Страница 56: ...507716 01 Page 56 of 58 Issue 1717 Start Up Performance Checklist...