![Comelit 30001008 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/comelit/30001008/30001008_technical-manual_2640413030.webp)
30
Addressing the BUS and setting its speed via dip switch
Note that the standard
speed
of the bus for VEDO control panels is 38400 baud.
The device address
must be unique and can only be programmed using dip switches.
DIP4
DIP5
DIP6
not
used
No.
DIP1
DIP2
DIP3
1
OFF
OFF
OFF
2
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
5
OFF
OFF
ON
6
ON
OFF
ON
7
OFF
ON
ON
8
ON
ON
ON
BAUD
DIP7
DIP8
9600
OFF
OFF
38400
(default)
ON
OFF
57600
OFF
ON
115200
ON
ON
Terminal block description
Earth
Earth connection terminal
BUS IN
V+
485 communication BUS power supply input positive
V-
485 communication BUS power supply input negative
A
RS485 data BUS for connection to the control panel (IN) - A
B
RS485 data BUS for connection to the control panel (IN) - B
BUS OUT
V+
Power supply positive output. 485 communication bus. Limited to 1.5A
V-
Power supply negative - output reference. 485 communication BUS power supply
A
RS485 data BUS for connection to other devices (OUT) - A
B
RS485 data BUS for connection to other devices (OUT) - B
OUTPUTS POWER SUPPLY
V+AUX1
Auxiliary 1 power supply output positive. Limited to 1.5A
V-
Auxiliary 1 power supply output negative
V+AUX2
Auxiliary 2 power supply output positive. Limited to 1.5A
V-
Auxiliary 2 power supply output negative
24H
Tamper contact input
OUTPUTS
O1
Open collector output 1.
Programmed as module Anti-Sabotage by default. The output is active when module sabotage occurs.
O2
Open collector output 2.
Programmed as module Low Battery Anomaly by default. The output is active when the programmed time has elapsed since
the moment at which the battery was no longer detected or the voltage at its terminals is 10.7 Vdc or 15 Vdc.
O3
Open collector output O3.
Programmed as module No 230V Mains Anomaly by default. The output is active when the programmed time has
elapsed since the moment at which the network was no longer detected.
Con
fi
guration jumpers
JP1
RS485 output termination*
JP2
RS485 input termination*.
* Always remember to insert an end-of-line resistor between A and B of the 485 connection (using the relevant jumpers) to the two ends of the
main BUS line.
LED signals
DL1
Flashing slowly:
no data transfer over BUS at the speed set using the dip switch.
Flashing quickly:
data transfer over BUS in progress.
DL2
Off:
the peripheral is communicating correctly.
Very slow
fl
ashing:
(approx. 3 seconds) no data package on the BUS.
DL3
On:
indicates that one of the Open Collector outputs is under protection due to a short circuit.
PSU connector
J1
External 230 V - 50 Hz power supply unit connector
The
24H
terminal needs the Tamper contact to be connected in single balanced con
fi
guration.
A resistance of
1.8K
Ω
, in series with the contact, is required.
Tamper contact connection
ALARM
SINGLE BALANCED