InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 78
IL-NT-AMF-2.2-Reference Guide.pdf
Step:
1 s
Range: 0
– 900 s
Hint:
First analog input is dedicated to Oil Pressure measurement. It is not supposed to be used for
measurement of other values.
AI2 Wrn
[ ]
Warning threshold level for ANALOG INPUT 2
Step:
1
C
Range: -100
– 10000
AI2 Sd
[ ]
Shutdown threshold level for ANALOG INPUT 2
Step:
1
C
Range: -100
– 10000
AI2 Del
[s]
Delay for ANALOG INPUT 2 alarm.
Step:
1 s
Range: 0
– 900 s
AI3 Wrn
[ ]
Warning threshold level for ANALOG INPUT 3
Step:
1 %
Range: -100
– 10000
AI3 Sd
[ ]
Shutdown threshold level for ANALOG INPUT 3
Step:
1 %
Range: -100
– 10000
AI3 Del
[s]
Delay for ANALOG INPUT 3
Step:
1 s
Range: 0
– 900 s
Batt Undervolt
[V]
Warning threshold for low battery voltage.
Step:
0,1 V
Range:
8V
– 40 (Battery >Volts)
Batt Overvolt
[V]
Warning threshold for hi battery voltage.
Step:
0,1 V
Range:
8V
– 40 (Battery <Volts)
Batt Volt Del
[s]
Delay for low battery voltage alarm.
Step:
1s
Range:
0
– 600 s
WrnMaintenance
[h]
Counts down when engine running. If reaches zero, an alarm appears. When the value 10000 is set,
than the Maintenance function is disabled and counter does not count. Counter value disappear in
controllers statistics. Maximum value for running countdown is 9999.