InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 60
IL-NT-AMF-2.2-Reference Guide.pdf
Mode MAN
The output is closed, if MAN Mode is selected.
Mode AUT
The output is closed, if AUT Mode is selected.
Mode TEST
The output is closed, if TEST mode is selected.
AL D+ Fail
Output closes if gen-set is running and D+ input not energized.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Hint:
Threshold level for D+ input is 80% supply voltage.
AL Gen >V
The output closes if the generator overvoltage shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen <V
The output closes if the generator undervoltage shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen Volts
The output closes if the generator over/under voltage alarm or voltage asymmetry alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen Freq
Output closes if the generator over/under frequency alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen >Freq
Output closes if the generator over frequency alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL Gen <Freq
Output closes if the generator under frequency alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed