InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 113
IL-NT-AMF-2.2-Reference Guide.pdf
3. For Split Ph:
a. Vg1 = Gen. Ph-Ph voltage L1-L2
b. Vg2 = Gen. Ph-N voltage L2
c. Vg3 = Gen. Ph-N voltage L1
4. For Mono Ph:
a. Vg1 = Gen. Ph-N voltage L1
b. Vg2 = 0
c. Vg3 = 0
The mains voltages are displayed in history analogously.
Hint
:
To force history download in LiteEdit (direct, modem or Internet) open History window and select
History | Read history command.
Hint
:
The first history record after the controller is switched on, programmed or watchdog reset occurs
contains diagnostic values instead of operational. Some fields in these records seem to have
nonsense values. Do not take these values into account.
Hint
:
Some of the
controller models doesn´t have RTC. In this case there is no Date column and the Time
column contains information about running hours.
Record structure
Abbreviation
Historical value
Num
Number of historical event
Reason
Event specification
Date
Date of historical event in format DD/MM/YY
Time
Time of historical event in format HH:MM:SS
Mode
Controller’s mode
RPM
Engine speed
Pwr
Generator active power
PF
Generator PF
LChr
Character of the load
Gfrq
Generator frequency
Vg1
Generator voltage L1-L2 or *see description above
Vg2
Generator voltage L2-L3 or *see description above
Vg3
Generator voltage L3-L1 or *see description above
Ig1
Generator current L1
Ig2
Generator current L2
Ig3
Generator current L3
Mfrq
Mains frequency
Vm1
Mains voltage L1-L2 or *see description above
Vm2
Mains voltage L2-L3 or *see description above
Vm3
Mains voltage L3-L2 or *see description above
UBat
Battery voltage
OilP
IL-NT Analog input 1 value ( default Oil pressure)
EngT
IL-NT Analog input 2 value ( default Water temperature)
FLvl
IL-NT Analog input 3 value ( default Fuel Level)
BIN
Binary inputs IL-NT
BOUT
Binary outputs IL-NT
BIOE*
Binary inputs/outputs plug-in module (when IL-NT-BIO8 module is configured)
FC*
ECU alarm FailureCode (when ECU is configured)
FMI*
ECUalarm Failure Mode Identifier (when ECU is configured)
AIM1*
IG-IOM, IGS-PTM Analog input 1 value (when configured IG-IOM, IGS-PTM)
AIM2*
IG-IOM, IGS-PTM Analog input 2 value (when configured IG-IOM, IGS-PTM)
AIM3*
IG-IOM, IGS-PTM Analog input 3 value (when configured IG-IOM, IGS-PTM)