InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010
55
IA-NT- STD-2.0-Reference Guide.pdf
ion using external RS232-RS422/485 converter:
485 bus
0 or 56000 bps.
Any connected RS 232 to RS 422/485 converter has to be set to passive DSR signal (when DSR
connected) after switch on.
Alternative connect
Recommend external converter:
ADVANTECH – ADAM 4520: RS232 to RS422/485 converter, DIN rail, automatic RS
supervision, no external data flow control signals, galvanic isolated, baud rate 3840
Function description
Remote display IL-NT-RD works as remote display and control of the master Inte
InteliDrive Lite controller. It is supposed and highly recommended that both, remote
master are using the same HW type and model of controller. Another types and models of mast
remote display are not supported nor tested. All remote display
liATS
NT
, InteliLite
NT
or
display and
er and
’s LEDs show the same state as
ork in the same
ntroller. User can
switch screens, set password, change setpoints and view history records.
Interruption of the serial line between master device and Remote display has no effect to the master
unication cannot be
nfiguration table
After the configuration from master is downloaded remote display jump to master controllers Init
and blinking.
een to check it’s version and serial number of used
essing PAGE button for 3 seconds.
SW compatibility
corresponding LEDs on master controller. Front panel buttons on both controllers w
way. Genset/Engine can be controlled from remote display as well as from master co
All IL-NT-RD screens Init, Measure, Setpoints and History display the same data like in the master
controller.
Master device is always able to work without connected Remote display.
controller.
If the serial line between master device and remote display is interrupted, or comm
established, remote display shows it’s Init screen and message “Trying” and all LED’s are off.
Once remote display finds compatible master it shows “Preparing” and downloads co
from master controller.
screen and all LEDs
It is possible to switch to remote displays Init scr
controller and communication status by pr
IL-NT-RD sw. version 1.0 is compatible with masters SW:
•
All InteliATS
NT
standard software from ver. 1.0
•
All InteliLite
NT
standard software from ver. 1.1
•
All ID-Lite standard software from ver. 1.0
•
Chosen InteliATS
NT
, InteliLite
NT
and ID-Lite customer branches
Some of the future InteliATS
NT
, InteliLite
NT
, ID-Lite versions may require upgrade of the IL-NT-RD
software.