InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010
50
IA-NT- STD-2.0-Reference Guide.pdf
ging
Remote Control and Data Log
Direct connection to the PC
InteliATS
NT
can be connected directly with PC via optional IL-NT RS232 interface.
Use the standard serial cable to connect PC with InteliATS
NT
.
N
OTE
:
Make sure the grounding system on controller and PC – COM port (negative of the PC DC supply) are
identical – before the first direct connection. There must not be any voltage between these two points
otherwise the internal reversible fuse in controller burns out. The simple solution is to assure, that the
PC supply 240/20V is ground free (GND terminal is not connected).
5 - GND
2 - RxD
3 - TxD
PC
5 - GND
2 - RxD
3 - TxD
RS
23
2
RS
23
2
230 VAC
0 V
D
C
CONTROLLER
+
-
Battery
Required the same
voltage potential
between GND‘s
RS 232
PC software – LiteEdit
On the PC (fo
n) has to be installed the ComAp’s software package
LiteEd
rm)
LiteEdit enabl
•
control the engine
•
configure the controller
•
select software configuration
•
modify alarm inputs and outputs
•
modify password, commands protections
•
direct, modem or Internet communication
r direct or modem connectio
it. (based on Windows 95 or newer platfo
es:
•
read the quantities
•
adjust all set points