background image

 

InteliATS

NT

 STD, SW version 2.0, ©ComAp – June 2010 

                                             56 

IA-NT- STD-2.0-Reference Guide.pdf 

ta 

I

/O

u

v

e

Technical Da

nputs

utp ts o ervi w 

Model 

IN 

UT

OM

COM

Gen

Voltage

Mains 

Voltage

B

BO

  C

2

IA-NT STD 

4 (3**) 

Y*

Y*

Y

Y

 
N

OTE

:

 

 

* With optional plug-in module 
** Hardware version 1.3 provides 3 inputs only 
Y -Available 

 
Power supply 

 
Voltage 

supply 

     8-36V 

DC 

Consumption   

 

 

 

 

40-430mA depend on supply voltage and 

 
Consumption depends on supply voltage 

 

0,104A at   8VDC  

VDC 

 

 

 

 

0,044A at 30VDC 

36VDC 

p-out:   

 

 

100ms from min. 10V, return to min. 8V 

ent tolerance  

 

2 % at 24V 

 

       temperature 

 

 

 

 

 

 

 

0,080A at 12VDC 

 

 

 

 

 

 

 

0,051A at 24

 

 

 

0,040A at 

 
Allowed supply voltage dro
Battery voltage measurem

N

OTE

:

 

 

For the supply voltage less than 7V the backlight of the display is switched off. 
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all. 

Operating conditions 

 
Operat

 

 -20..+7

Storage 

r

ing 

temperature 

IA-NT 

 

0

o

temperatu e 

    -30..+80

o

 

Humidity      95% 

without 

condensation 

   EN 

61010-1:95 

+A1:97 

Electromagnetic Compatibility   

 

 

EN 50081-1:94, EN 50081-2:96 

:99, EN 50082-2:97 

- 25 Hz, ±1,6mm  

25 - 100 Hz, a = 4 g 

Shocks 

      a 

200 

m/s

2

  

Dimensions and weight 

Protection 

front 

panel 

    IP65

Standard conformity 
Low 

Voltage 

Directive 

 

 

 

 

 

 

 

 

EN 50082-1

Vibration  

 

 

 

 

 

 
Dimensions 

     180x120x55mm 

Weight 

      450g 

Содержание IA-NT STD

Страница 1: ...Prague Czech Republic ComAp spol s r o Kundratka 2359 17 180 00 Praha 8 Czech Republic Tel 420 246 012 111 Fax 420 266 316 647 E mail info comap cz www comap cz Reference Guide Automatic Transfer Swit...

Страница 2: ...IL NT RS232 Communication module IL NT RS232 485 Communication module IL NT S USB Service USB communication module IL NT RD Remote display software IB Lite Communication module IL NT BIO8 Hybrid binar...

Страница 3: ...Remote Control and Data Logging Direct connection to the PC PC software LiteEdit Remote Communication Internet connection Recommended ISDN modem Recommended GSM modem Mobile SIM card setting IL NT RD...

Страница 4: ...justment etc which can cause a damage or unproper function of the equipment if not performed correctly and may not be clear at first sight WARNING This type of paragraph indicates things procedures ad...

Страница 5: ...d used when a low temperature ATS application is needed In this case the Inteli combined purchased with the IL NT AMF 25 LT HW to obtain the low tempe NOTE Because of large variety of InteliATSNT para...

Страница 6: ...Switch InteliATSNT to MAN or OFF Mode or disconnect the Binary outputs Rem Start Stop and GCB Close Open to avoid unexpected automatic start of gen set and GCB closing WARNING Dangerous voltage In no...

Страница 7: ...ion Factory default configuration covers most of applications Different customer changes are possible thanks to the configurability Excellent remote communication capabilities High reliability remote...

Страница 8: ...e then equals to 20 ms breaker reaction time HINT Use longer delay time to avoid problems with motor starters Motor starts prefer to see break of a few seconds so they can initialize properly HINT To...

Страница 9: ...InteliATSNT STD SW version 2 0 ComAp June 2010 9 IA NT STD 2 0 Reference Guide pdf Example application...

Страница 10: ...hanged only using PC and Lit LiteEdit documenta NOTE You need one of communication modules to connect the controller to a PC with LiteEdit There is a special easy removable service module for cases wh...

Страница 11: ...first use screwdriver to open and then module into slot Once you ha insert the ve inserted it the module will snap under plastic teeth It is supposed to be installed permanently Should you need to rem...

Страница 12: ...InteliATSNT STD SW version 2 0 ComAp June 2010 12 IA NT STD 2 0 Reference Guide pdf 4 Break apart the small cover into two pieces Do not throw away the smaller part 5 Take RS 232 communication module...

Страница 13: ...slot of the controller 7 Put back the small cover 6 Plug RS 232 comm NOTE When you insert RS 232 communication module the boot jumper is hidden For that reason we recommend to use RS 232 communication...

Страница 14: ...ions for IL NT RS232 module procedure i You must open the cover first use screwdriver to open and then insert the module into have insert it the module RS485 RS232 Boot jumper RS485 Terminator jumper...

Страница 15: ...NT RD Remote display software chapter for more details module IB Lite Communication IB Lite is optional plug in card to enable InteliATSNT communication via Ethernet Intern into expansion slot back on...

Страница 16: ...InteliATSNT STD SW version 2 0 ComAp June 2010 16 IA NT STD 2 0 Reference Guide pdf Scada window Measurement window...

Страница 17: ...STD SW version 2 0 ComAp June 2010 17 IA NT STD 2 0 Reference Guide pdf Setpoints window History window HINT This feature requires IB Lite optional plug in module and visible connection of controller...

Страница 18: ...nary input output module IL NT BIO8 is optional plug in card Through this card controller can accommodat inputs or outputs In LiteEdit PC configuration tool version 4 4 and higher it is possible to ea...

Страница 19: ...Please see latest IA NT Operators Guide for detailed description User Interfac There is an interchangable User Interface on controller It allows two different mode controller menu The first mode calle...

Страница 20: ...InteliATSNT STD SW version 2 0 ComAp June 2010 20 IA NT STD 2 0 Reference Guide pdf s IA NT STD terminals and face Terminal...

Страница 21: ...2 0 Reference Guide pdf Installation Mounting The controller is to be mounted onto the switchboard door Requested cutout size is 175x115mm Use the screw holders delivered with the controller to fix t...

Страница 22: ...STD Wiring Diagram Recommended Wir L1 L2 L3 N DIESEL GAS ENGINE GENERATOR G RS 232C Interface Modem or PC II REM TRANSFER MAINS FAIL BLOCK REMOTE AUT GCB CLOSE OPEN GEN START STOP NEUTRAL POS MCB CLO...

Страница 23: ...akers MCB and GCB Application The most typical application for the ATS controllers is Auto Mains Failure AMF ap controller watche mains x generator G IA NT GCB 3x LOAD 3xU M 3xU G MCB 3x T 3x K4 MCB G...

Страница 24: ...x 3xU M 3xU G 3x T 3x GCB CLOSE OPEN BO K3 LOAD ATS 3x ATS I II Specification set start when the mains fails AUT mode fer on mains failure Break return on mains return Load reclosing Test mode set run...

Страница 25: ...SE OPEN GCB CLOSE OPEN BO LOAD ATS 3x ATS I II 0 K4 K3 Specification Automatic remote gen set start when the mains fails AUT mode control pass through neutral position fer on mains failure Break retur...

Страница 26: ...II 0 Force Neutral Position Manual Load Transfer K3 K4 K5 NEUTRAL POS set start when the mains fails AUT mode control pass through neutral position est for load transfer AUT mode Request for switching...

Страница 27: ...ions B closed and the 24V AC DC power supply source is locked in gen set If Mains GCB is opened 24V AC DC power supply source is unlocked and switched to Mains MCB is closed Gen set is stopped Hardwar...

Страница 28: ...art Stop GenreadyToLoad Specification Controllers are suitable for Cascading applications allowing load to be split into The followi ave to be fulfilled more sections Automatic remote gen set start wh...

Страница 29: ...W version 2 0 ComAp June 2010 29 IA NT STD 2 0 Reference Guide pdf Cascade wiring B Mains Fail timing diagram with configuration description Cascade wiring B Mains Return timing diagram with configura...

Страница 30: ...T ting strikes The maximum allowable current through the controller s negative terminal is 4A this is dependent on binary output load For the connections with 12VDC power supply the InteliATSNT includ...

Страница 31: ...on of controller and display heating element is on below 5 C Current drain of heating element exhausts LBA capacitors very fast nected in line with the battery positive terminal to the controller and...

Страница 32: ...InteliATSNT STD SW version 2 0 ComAp June 2010 32 IA NT STD 2 0 Reference Guide pdf IL NT BIO8 extension module connection...

Страница 33: ...ithout N are needed Switchboard lighting strikes protection according standard regulation is expected Single phase applications There is not a separate archive file for single phase applications Use s...

Страница 34: ...InteliATSNT STD SW version 2 0 ComAp June 2010 34 IA NT STD 2 0 Reference Guide pdf Binary inputs Binary outputs Battery iL 4k7 Power Supply Battery iL LOAD Power Supply...

Страница 35: ...ut is not connected Alarm If the input is closed or opened sel d alarm is activated ecte Bina nfigu ms string ry Alarm co ration ite Name 14 characters ASCII NC Normally closed Contact type NO ally op...

Страница 36: ...is closed or opened MainsHealthy This iinp s creted mainly for cascading applications where slave controllers do not have usually Mains and Gen set voltage measuring inputs connected to the repspectiv...

Страница 37: ...n the gen set start is requested and opens after the AMF Setti Time has elapsed Afterwards the GenStart Stop output is activated as a start signal for the re Pretransfer Is ac a resu of tiv ted during...

Страница 38: ...STD 2 0 Reference Guide pdf tes when the controller is not in AUT mode S switch to its neutral position The output is a copy of Fault Reset button on controller and binary input FaultResButton Not In...

Страница 39: ...sing LiteEdit software eq Hz 65 Hz e s ut prior to the engine start zero t to leave the output Prestart Pretzransfer open MaxStartDel s This timeout starts after closing binary output GEN START STOP W...

Страница 40: ...e 360 n he controller doesn t care for the engine is stopped Trp Stop Fail is never announced GenStart Logic CLOSE ON CLOSE OFF The set point influences the behavior of the output Gen Start Stop CLOSE...

Страница 41: ...vailable only in AMF8 9 Test Duration Time interval Range 0 240 minutes Available only in AMF8 9 NOTE This function does not work till both setpoints Test Period and Test Duration are set to non zero...

Страница 42: ...Del MCB lose Open MCB Feedback GCB Close Open C Mains Threshold for mains overvoltage All three phases are checked Maximum out of t V Step 1 Range Mains V Mains V Threshold for mains undervoltage All...

Страница 43: ...not No autostart is performed No re CB can be tton action to the input Rem Start Stop NOTE The engine can run without load unlimited time The controller does not automatically stop the running gen set...

Страница 44: ...Island operation uency OK D Mains return Mains voltage and freq MainsReturn started el timer Mains failed Island operation Mains return e stop 3 Mains operation MainsReturnDel elapsed GCB CLOSE OPEN o...

Страница 45: ...red mains electrical limits voltage frequency are still in limits the controller switches MCB ON again EmergStart Del Mains fail MCB opened Preset delay genset start Relation between Mains return and...

Страница 46: ...InteliATSNT opens outputs GCB CLOSE OPEN GENSTART STOP p the engine immediately Alarm outputs and common shutdown output are closed Active or not reset protection disables start s and PRESTART to sto...

Страница 47: ...W version 2 0 ComAp June 2010 47 IA NT STD 2 0 Reference Guide pdf AMF time chart genset OK AMF time chart genset not started properly Hint Please see the AMF Setting MaxStartDel setpoint description...

Страница 48: ...portant after c oltage terminals ontroller installation to avoid wrong voltage phases phase s can be detected The T controller L1 L2 L3 When the phases are conn 2 L1 L3 following alarms are detected G...

Страница 49: ...ry input Configurable YE arning Shutdown S Configurable W alarms on the inputs of IA NT Trp BatteryFlat TRP YE es off during to bad battery try to start again ection S If the controller switch startin...

Страница 50: ...internal reversible fuse in controller burns out The simple solution is to assure that the PC supply 240 20V is ground free GND terminal is not connected 5 GND 2 RxD 3 TxD PC 5 GND 2 RxD 3 TxD RS232...

Страница 51: ...s Start Program files LiteEdit Gm_setup exe Select COM port ress S Wavecom M1 Wavecom Maestro 20 dual 900 1800MHz Wavecom Fastrack M1306B dual 900 1800 MHz Fastrack M1206B is NO FALCOM A2D dual 900 18...

Страница 52: ...is highly recommended to use the same type and model of controller for master and remote d the proper function of all buttons LED diods and display play are display Only in such case is assure Anothe...

Страница 53: ...COM2 from address 1 to 32 Remote display tries two communication speeds 38400 bps and 56000bps Detecting on screen and progress bar below counts from 0 to prox 10 15 seconds Than is 5 seconds pause an...

Страница 54: ...for direct IA NT I ale RxD 2 3 TxD TxD 3 2 RxD GND 5 5 GND Remote RS485 and or direct RS232 connection HW module IL NT RS232 485 Up to 1000 meters only with RS485 Case 1 RS232 Master controller setti...

Страница 55: ...ble After the configuration from master is downloaded remote display jump to master controllers Init and blinking een to check it s version and serial number of used essing PAGE button for 3 seconds S...

Страница 56: ...tolerance 2 at 24V temperature 0 080A at 12VDC 0 051A at 24 0 040A at Allowed supply voltage dro Battery voltage measurem NOTE For the supply voltage less than 7V the backlight of the display is switc...

Страница 57: ...Number of outputs Maximum current 0 5 Maximum switching voltage IL NT RS232 interface optional card Plugs into IA NT controller COMMUNICATION MODULE port Maximal distance 10m Up to 57 6 kBd DIRECT 38...

Страница 58: ...o C Operating temperature Storage temperature IL NT BIO8 extension module optional card Technical details 8 plugs into the controller s EXTENSION MODUL al can be config ary inputs or outputs 8 4 7 k 0...

Отзывы: