BLOWDOWN SEPARATOR (Optional)
The blowdown separator design incorporates an internal water seal at the outlet, which
permits the operator to introduce cold water from the bottom to mix with the hot water from
the boiler blowdown. This reduces the outlet water temperature for safe discharge.
If the separator is less than half full of water after the boiler is blown down, cold tap water
must be added to bring the water level to the half-way mark before the next blowdown.
The vent must be piped, full size, to a safe location so that steam flashing off the blowdown
will not injure individuals or damage equipment.
Do not reduce the outlet pipe or vent pipe size coming off of the tank.
BLOWDOWN SEPARATOR
Figure 9
Содержание CT Series
Страница 2: ...CT BOILER WITH PARTIAL SECTION Figure 1 ...
Страница 13: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 10 Figure 4 BLOWDOWN PIPING ...
Страница 34: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 31 MAINTENANCE LOG ...
Страница 35: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 32 MAINTENANCE LOG ...
Страница 48: ...APPENDICES ...
Страница 58: ......
Страница 60: ...OPERATION OF WARRICK DUAL FUNCTION CONTROLS 5 95 PRINTED IN U S A ...
Страница 61: ...INSTALLATION OF WARRICK SERIES 3C 3K ELECTRODE FITTINGS ...
Страница 62: ......
Страница 63: ...OPERATION OF WARRICK SERIES 26 CONTROLS 5 93 ...
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 71: ......