FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 39 -
WATER TREATMENT
Proper treatment of make-up water and boiler water is necessary to prevent scale, or other
deposits, and corrosion within the boiler. The absence of adequate external and internal
treatments can lead to operational upsets or total boiler failure. Where a choice is avail-
able, pretreatment external to the boiler is always preferred and more reliable than treat-
ment within the boiler.
Instructions for feed water treatment as prepared by a competent feedwater chemist should
be followed. Do not experiment with homemade treatment methods or compounds.
Representative samples of feed water and boiler water must be analyzed frequently to
ensure that they are in specification.
the following terms and guidelines are to be used in
conjunction with the advice of a water treatment specialist.
Recommended Guidelines for Boiler Water Treatment
RECOMMENDED
ANALYSIS
COMMENTS
RANGE
pH
10-11
Low pH promotes corrosion
Total Alkalinity
200-700 ppm
Low: promotes corrosion
Phosphates
30-100 ppm
Prevent scale formation
Total Hardness
0-50 ppm
Prevents scale formation
Chlorides
60-200 ppm
A measure of proper blow down
Total Dissolved Solids
2000 ppm Maximum
High solids may cause surging
Sulfites
20-30 ppm
A good oxygen scavenger
Specific Conductance
< 700 micro ohms cm
A measure of proper blowdown
Oxygen
< .007 mg/liter
Prevents corrosion and pitting
ppm = parts per million
Use proper water treatment
to prevent the buildup of scale
on the boiler. After scale has
built up on the walls of the boiler it is almost impossible to remove it from the boiler. The
introduction of acids into the pressure vessel is thoroughly discouraged, since virtually any
solution that will chemically attach the scale will also attack the boiler metal.
pH
The pH value of the boiler water is a number between zero and fourteen. Values below
seven are acidic, seven is neutral, and values above seven ar alkaline.
The pH factor is the most important factor influencing scale formation and the corrosive ten-
dencies of boiler water. The pH should be maintained between a minimum of 10.5, and
a maximum of 11.0 to prevent acidic corrosion of boiler tubes and plates, and to provide
Содержание CT Series
Страница 2: ...CT BOILER WITH PARTIAL SECTION Figure 1 ...
Страница 13: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 10 Figure 4 BLOWDOWN PIPING ...
Страница 34: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 31 MAINTENANCE LOG ...
Страница 35: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 32 MAINTENANCE LOG ...
Страница 48: ...APPENDICES ...
Страница 58: ......
Страница 60: ...OPERATION OF WARRICK DUAL FUNCTION CONTROLS 5 95 PRINTED IN U S A ...
Страница 61: ...INSTALLATION OF WARRICK SERIES 3C 3K ELECTRODE FITTINGS ...
Страница 62: ......
Страница 63: ...OPERATION OF WARRICK SERIES 26 CONTROLS 5 93 ...
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 71: ......