FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 18 -
All through the wall connections must adhere to safety standards set forth by standard
building practices and local codes. In the absence of local codes, UL listed wall thimbles
and through the wall connectors should be used.
The combustion vent cap must extend a minimum of four feet from the building, and must
be located as far from the combustion air intake as possible. The combustion vent must ter-
minate a minimum of seven feet above the ground where pedestrian traffic can be expect-
ed. It shall also terminate at least three feet above any forced air inlet within ten feet, and
shall terminate at least four feet below or four feet horizontally from, or one foot above and
two feet horizontally from, any door, window, or gravity air inlet into any building as pro-
vided in the National Fuel Gas Code NFPA 54. See Figure 6.
Both the Combustion Flue
Vent and the combustion Air Intake must be in the same wall.
COMBUSTION VENT LOCATIONS
Figure 6
Combustion Air Intake
The air for combustion must be ducted directly to the burner intake and must terminate out-
side with the applicable Intake Air cap listed in the Table on page 15. The vent cap can
be installed either horizontally or vertically in conjunction with a tee. It is suggested that a
screen or vent pipe plug be inserted into the bottom of the tee to prevent animals and other
matter from entering. The maximum length of combustion air intake duct shall be 40 feet.
The combustion air intake shall be full size for the complete run and shall not have more
than four 90° elbows. The combustion air intake cap must be at least one foot off the
ground in an area that is always free from obstructions.
The Combustion Air Intake must
be in the same wall as the Combustion Vent.
Important Note: Surface discoloration of the building may occur due
to improper boiler/burner adjustment and maintenance. Columbia
Boiler Company will not accept any liability for such discoloration.
Содержание CT Series
Страница 2: ...CT BOILER WITH PARTIAL SECTION Figure 1 ...
Страница 13: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 10 Figure 4 BLOWDOWN PIPING ...
Страница 34: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 31 MAINTENANCE LOG ...
Страница 35: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 32 MAINTENANCE LOG ...
Страница 48: ...APPENDICES ...
Страница 58: ......
Страница 60: ...OPERATION OF WARRICK DUAL FUNCTION CONTROLS 5 95 PRINTED IN U S A ...
Страница 61: ...INSTALLATION OF WARRICK SERIES 3C 3K ELECTRODE FITTINGS ...
Страница 62: ......
Страница 63: ...OPERATION OF WARRICK SERIES 26 CONTROLS 5 93 ...
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 71: ......