![Columbia CT Series Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/columbia/ct-series/ct-series_installation-operation-and-maintenance-manual_2638309025.webp)
FM-148 COLUMBIA BOILER COMPANY, REV 6-06
- 22 -
pump motor switches of the Warrick Series DF Low Water cut Off and Pump Control. A
Motor Starter also provides electrical overload protection for the feedwater pump motor.
A Motor Contactor is provided as standard equipment on the CT-6 thru CT-25 Boilers, and
a Motor Starter is provided as standard equipment on the CT-35 and CT-50 Boilers.
Warrick Series 26 Probe Type Low Water Cut-Off
The manual reset “probe” is used as a supplementary safety device for protecting the boil-
er against damage from low water. It is designed to operate if the Series DF low water cut-
off should fail to operate for any reason. This unit is set to operate at a water level in the
boiler lower than that of the Warrick Series DF. See drawing CT-415 in the appendix for
installation of probe rod.
This unit consists of a circuit board design with one normally open (N.O.) non-powered
contact. When reset, it completes a circuit between the probe rod and the boiler drum,
through the water in the boiler. If the water level falls below the probe rod, the circuit is
broken causing the contact to open, breaking the circuit to the burner and energizing an
alarm circuit (if equipped).
NOTE:
This relay must be reset after a low water condition has been corrected or after
any interruption in the electrical supply.
DESCRIPTION OF OPERATING CONTROLS AND SAFETY DEVICES
Operating Pressure Control
The operating pressure consists of a pressure actuated switch with an adjustable differen-
tial. This switch opens on pressure rise. It should be set at the maximum operating pressure
desired.
Do not
set the operating pressure higher than 135 PSI. the differential determines
when the burner will restart. The differential should be set at a value as large as possible
to keep the unit from short cycling.
The pressure control must be level in order to operate accurately. It is level when the level-
ing indicator hangs freely with its pointer directly over the index mark inside the back cover
of the case.
The upper operating or cut-off pressure is determined by the main scale set point, while the
lower operating or cut-in pressure is determined by the main scale operating point minus
the differential.
Adjust the main scale set point for the desired operating pressure by turning the main scale
adjusting screw on top of the case until the main scale setting indicator is at the desired
pressure. Adjust the differential set point for the desired cut in pressure by turning the
adjusting screw on top of the case until the differential setting indicator is at the desired
setting.
Содержание CT Series
Страница 2: ...CT BOILER WITH PARTIAL SECTION Figure 1 ...
Страница 13: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 10 Figure 4 BLOWDOWN PIPING ...
Страница 34: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 31 MAINTENANCE LOG ...
Страница 35: ...FM 148 COLUMBIA BOILER COMPANY REV 6 06 32 MAINTENANCE LOG ...
Страница 48: ...APPENDICES ...
Страница 58: ......
Страница 60: ...OPERATION OF WARRICK DUAL FUNCTION CONTROLS 5 95 PRINTED IN U S A ...
Страница 61: ...INSTALLATION OF WARRICK SERIES 3C 3K ELECTRODE FITTINGS ...
Страница 62: ......
Страница 63: ...OPERATION OF WARRICK SERIES 26 CONTROLS 5 93 ...
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 71: ......