13 

NOTE: 

 

These conversions should only be carried out 
by qualified persons.  All connections must be 
checked  for  leaks  before  re-commissioning 
the appliance. 

 

For  all  the  following  conversion  instructions, 
the side panels have to be removed (Remove 
the  two  screws  at  the  bottom  of  each  side 
panel). 

 

All  conversion  details  apply  to  both  L/Hand 
and R/Hand burners. 

 

For  all  relevant  gas  specifications  refer  to  the 
table at the end of this section. 

 

1.  Ensure that the gas supply has been turned 'Off'. 
2.  Unscrew the main burner injectors (

½

” A/F). 

 

3.  Determine the correct injector sizes for the  

corresponding gas type from the rating plate 
affixed to the right hand side panel front bottom 
corner. 

4.  Replace with the correct size injectors. 

Main Burner 

Injector 

1.  Remove the gas control knobs from the front of 

the unit. 

2.  Remove the 2 front control panels by removing 

the two screws (per panel) located at the  
bottom of each panel. 

3.  Set the burner low fire adjustment.  Low fire 

screw on gas control valve should be screwed 
fully in, then unscrewed by the measurement 
shown in the ‘Gas Specifications’ table. 

NOTE: 
The ‘Low Fire Screw’ should be sealed with coloured 
paint on completion of low fire adjustment. 

 
 

Before leaving the converted installation; 
1.  Check  all  gas  connections  for  leakages  using 

soapy water or other gas detecting equipment. 

2.  Check the following functions in accordance 

with the operating instructions specified in the 
‘Operation’ section of this manual. 

 

Light the Main Burners. 

 

Check the Low Fire burner operation. 

 

Check the High Fire burner operation. 

 

Ensure all controls operate correctly. 

 

NOTE: 
If  it  is  not  possible  to get  the  appliance  to  operate 
correctly,  shut  off  the  gas  supply  and  contact  the 
supplier of this appliance. 
 
 

On  completion  of  the  gas conversion,  replace  the 
gas type labels located at:- 

- Rear of unit, above gas connection point. 
- Beside the rating plate. 

 

NOTE: 
If  it  is  not  possible  to get  the  appliance  to  operate 
correctly, shut ‘Off’ the gas supply and contact the 
supplier of this appliance. 

Low Fire  

Adjustment 

 

D

O

 

NOT

 

USE

 

A

 

NAKED

 

FLAME

 

TO

 

CHECK

 

FOR

 

GAS

 

LEAKAGES

Содержание CS9

Страница 1: ...Gas Salamander Model CS9 I N S T A L LA T I ON A N D OP E R A T I ON M A N U A L 242353 1 ...

Страница 2: ...00 337 963 Customer Service tel 1800 335 315 fax 1800 350 281 CANADA Serve Canada Web www servecanada com E Mail info servecanada com Sales tel 800 551 8795 Toll Free Service tel 800 263 1455 Toll Free NEW ZEALAND Moffat Limited Web www moffat co nz E Mail sales moffat co nz Main Office tel 0800 663328 UNITED KINGDOM Blue Seal Web www blue seal co uk E Mail sales blue seal co uk Sales tel 44 121 3...

Страница 3: ...es Wall Mounting To Non Combustible Wall Only Gas Connection Commissioning Operation Guide Description of Controls Lighting the Main Burners Racking System Cooking Recommendations General Racking Stainless Steel Surfaces Vitreous Enamel Surfaces Crumb Drip Tray Periodic Maintenance Gas Control Valve Re Greasing Gas Conversion Procedure Gas Specifications ...

Страница 4: ...ons for adapting the appliance to the conditions for use in that country IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE INJURY OR DEATH READ THE INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS APPLIANCE INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE USER SMELLS GAS ARE TO BE POSTED IN A PROMINENT LOCATIO...

Страница 5: ...ntrols Each main burner is provided with flame failure feature for ease of operation and safety The main burners are manually lit with each burner having LO to HI settings to provide full cooking flexibility Rack supports have 4 fixed height positions offering flat and angled rack positioning Cobra Salamanders come standard with a crumb drip tray for collection of cooking grease and crumbs from th...

Страница 6: ...4 CS9 Gas Salamander ...

Страница 7: ...that this salamander is installed correctly and that operation is correct before use Installation shall comply with local gas and health and safety requirements Waldorf Salamanders are designed to provide years of satisfactory service and correct installation is essential to achieve the best performance efficiency and trouble free operation This appliance must be installed in accordance with Natio...

Страница 8: ...e salamander is being added to an existing installation NOTE It is important that adequately sized piping runs directly to the connection joint on the appliance with as few tees and elbows as possible to give maximum supply volume NOTE Only non combustible materials can be used in close proximity to this appliance We recommend allowing a clearance of 100 mm on either side of the appliance to allow...

Страница 9: ...e manifold test point with two burners operating at the High Flame setting NAT LPG Butane Only The operating pressure is ex factory set and is not to be adjusted apart from when converting between gasses if required TOWN GAS Only The burner operating pressure is to be adjusted using the adjustable gas regulator supplied Refer to the Gas Conversion and Specifications section of this manual for furt...

Страница 10: ...ration practices can reduce the life of the salamander and produce a poor quality product To use this salamander correctly please read the following sections carefully Lighting the Main Burners Racking System Cooking Recommendations The salamander has individual heat controls for the left and right sides Select the desired heat level and allow a few minutes for the elements to heat up Cobra salama...

Страница 11: ...randing Plate under the burners before cooking commences also allows the sealed in flavoured goodness to be achieved TO AVOID THE RISK OF FIRE DO NOT LEAVE THIS APPLIANCE UN ATTENDED WHEN IN USE AS IT DOES COOK FAST DO NOT USE OR PLACE ANY COMBUSTIBLE MATERIAL WITHIN 600MM OF THE FRONT COOKING ZONE WHEN THE APPLIANCE IS IN USE SYSTEMATICALLY CHECK AND CLEAN THE COOKING AREA PARTICULARLY THE GRILL ...

Страница 12: ...son If any small faults occur have them attended to promptly Don t wait until they cause a complete breakdown It is recommended that the appliance is serviced every 6 months Clean the salamander regularly A clean appliance looks better will last longer and will perform better For ease of cleaning of this unit and the racking system and to achieve the best results it is recommended that the racking...

Страница 13: ...es by pulling the knobs away from the control panel 2 Remove the crumb drip tray from the appliance 3 Remove the two screws on the underside of the control panel securing the control panel to the hob 4 Remove the control panel from the front of the appliance 5 Remove the 2 screws holding shaft plate to gas control body and remove control shaft and plate Note orientation of shaft for correct re ass...

Страница 14: ...eleasing knob before thermocouple has heated Main Burner flame too small Gas pressure too low Partially blocked main injector Thermocouple faulty Hold knob in for at least 20 seconds following ignition of main burner Call service provider Call service provider Main burners will not light No gas supply Incorrect supply pressure Blocked main injector Faulty gas control Ensure gas isolation valve is ...

Страница 15: ...fire adjustment Low fire screw on gas control valve should be screwed fully in then unscrewed by the measurement shown in the Gas Specifications table NOTE The Low Fire Screw should be sealed with coloured paint on completion of low fire adjustment Before leaving the converted installation 1 Check all gas connections for leakages using soapy water or other gas detecting equipment 2 Check the follo...

Страница 16: ...ble on the flank of the pin once re fitted to the cap 4 Screw the cap back into the regulator hand tight only Town Gas Only 1 Unscrew and remove slotted cap from regulator 2 Turn On the gas supply and the appliance 3 Adjust pressure adjusting nut to achieve the correct burner operating pressure NOTE The operating pressure is to be measured at the manifold test point and with both burners operating...

Страница 17: ...Ø 1 00mm Ø 1 00mm Adjustment 2 turns out c c w turn out c c w Supply Pressure 1 13 3 40 kPa 2 75 4 50 kPa Burner Operating Pressure 1 0 kPa 2 55 kPa Gas Regulator Cap Screw Main Burner Injectors Ø 1 85mm Ø 1 15mm Low Fire Size Ø 1 00mm Ø 1 00mm Adjustment 2 turns out c c w turn out c c w Supply Pressure 1 13 3 40 kPa 2 75 4 50 kPa Burner Operating Pressure 1 0 kPa 2 55 kPa Gas Regulator Cap Screw ...

Страница 18: ...o the Gas Conversion and Specifications section of this manual for further details Main Burner Injectors Ø 1 85mm Ø 3 50 mm Low Fire Size Ø 1 00mm Ø 1 00 mm Adjustment 2 turns out c c w 4 turns out ccw Supply Pressure 1 13 3 40 kPa 0 76 1 50 kPa Burner Operating Pressure 1 0 kPa 0 63 kPa Gas Regulator Cap Screw Adjustable Regulator Adjust to the Burner Operating Pressure specified Main Burner Inje...

Страница 19: ...d 230671 Thermocouple General 026096 Wall Mounting Bracket 013908 Spacer Foot Assy 017963 Rack 026093 Side Rack 227961 Screw Side Rack 231546 Crumb Drip Tray Accessories Optional 013418 Branding Plate XP UK only Gas Regulators Gas Conversion Kits IMPORTANT Only genuine qualified replacement parts should be used for the servicing and repair of this appliance The instructions supplied with the parts...

Страница 20: ......

Отзывы: