![CLIVET WSAN-YMi 101 Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/clivet/wsan-ymi-101/wsan-ymi-101_instruction-manual-for-installation-use-and-maintenance_2625541076.webp)
ERROR
CODE
MALFUNCTION OR
PROTECTION
FAILURE CAUSE AND CORRECTIVE ACTION
P5
High Temperature difference
protection between water inlet and
water outlet of the plate heat
exchanger.
1. Check that all shut off valves of the water circuit are completely open.
2. Check if the water filter needs cleaning.
3. Refer to chapter WATER CONNECTIONS - Charging water"
4. Make sure there is no air in the system (purge air).
5. Check on the manometer that there is sufficient water pressure. The water
pressure must be >1 bar(water is cold).
6. Check that the pump speed setting is on the highest speed.
7. Make sure that the expansion vessel is not broken.
8. Check that the resistance in the water circuit is not too high for the pump. (refer
to START-UP AND CONFIGURATION - Setting the pump speed).
P6
Module protection
1. Power supply voltage of the unit is low, increase the power voltage to the
required range.
2. The space between the units is too narrow for heat exchange. Increase the
space between the units.
3. Heat exchanger is dirty or something is block on the surface. Clean the heat
exchanger or remove the obstruction.
4. Fan is not running. Fan motor or fan is broken, Change a new fan or fan motor.
5. Over charge the refrigerant volume. Recharge the refrigerant in right volume.
6. Water flow rate is low, there is air in system, or pump head is not enough.
Release the air and reselect the pump.
7. Water outlet temp sensor is loosen or broken, reconnect it or change a new
one.
8. water tank heat exchanger is smaller than the required 1.7m
2
.(10-16kW unit) or
1.4m
2
(5-9kW unit).
9. Module wires or screws are loosen. Reconnect wires and screws.
10. The Thermal Conductive Adhesive is dry or drop.Add some thermal conductive
adhesive.
11. The wire connection is loosen or drop. Reconnect the wire.
12. Drive board is defective, replace a new one.
13. If already confirm the control system has no problem, then compressor is
defective, replace a new compressor.
P9
DC fan motor protect
Contact your local dealer
Pd
High temperature protection of
refrigerant outlet temp of
condenser.
1. Heat exchanger cover is not removed. Remove it.
2. Heat exchanger is dirty or something is block on the surface. Clean the heat
exchanger or remove the obstruction.
3. There is no enough space around the unit for heat exchanging.
4. fan motor is broken, replace a new one.
Содержание WSAN-YMi 101
Страница 1: ......
Страница 18: ......
Страница 35: ...Type 2 Type 2 Type 2 Type 2...
Страница 42: ...T4 Outdoor Temperatures T1S set water temperature It is curve number 9 It can be set as shown in the figure...
Страница 43: ...T4 Outdoor Temperatures T1S set water temperature It is curve number 9 It can be set as shown in the figure...
Страница 84: ...Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions...
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 127: ......
Страница 128: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...