NOTE
In most applications this minimum water volume will be satisfactory.
In critical processes or in rooms with a high heat load though, extra water might be required.
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that this minimum water volu-
me is kept even if all the valves are closed.
Heighe difference is between the highest point of the wateer circuit and the outdoor unit's expansion tank.
Unless the unit is located at the highest point of the system, in which case the installation height differnce is considered to be zero.
The pre-pressure (Pg) to be set depends on the maximum installation height difference (H) and is calculated as follows: Pg(bar)=(H
(m)/10+0.3) bar
To determine the maximum allowed water volume in the entire circuit, proceed as follows:
Determine the calculated pre-pressure (Pg) for the corresponding maximum water volume using the graph below.
Check that the total water volume in the entire water circuit is lower than this value. If this is not the case, the expansion vessel
inside the unit is too small for the installation.
Maximum water volume (L)
Pre
ss
ur
e
(b
ar
)
Pre-pressure = pre-pressure of the expansion vessel
Maximum water volume = maximum water volume in the system
A1 System without glycol
A2 System without glycol
Содержание WSAN-YMi 101
Страница 1: ......
Страница 18: ......
Страница 35: ...Type 2 Type 2 Type 2 Type 2...
Страница 42: ...T4 Outdoor Temperatures T1S set water temperature It is curve number 9 It can be set as shown in the figure...
Страница 43: ...T4 Outdoor Temperatures T1S set water temperature It is curve number 9 It can be set as shown in the figure...
Страница 84: ...Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions...
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 127: ......
Страница 128: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...