WARNIG
Quando si ispeziona il quadro elettrico dell'unità, accertarsi sempre che l'interruttore generale sia spento.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it.
Under no circumstances can safety devices be bridged or changed to a value other than the factory setting.
If the cause of the problem cannot be found, call your local dealer.
If the pressure relief valve is not working correctly and is to be replaced, always reconnect the flexible hose attached to the pressure
relief valve to avoid water dripping out of the unit!
NOTE
For problems related to the optional solar kit for domestic water heating, refer to the troubleshooting in the Installation & Owner's
manual for that kit.
The unit is turned on but the unit is not heating or cooling as expected
POSSIBLE CAUSES
CORRECTIVE ACTION
The temperature setting is not
correct.
Check the controller set point.
T4HMAX,T4HMIN in heat mode.
T4CMAX,T4CMIN in cool mode.
T4DHWMAX,T4DHWMIN in DHW mode.
The water flow is too low.
Check that all shut off valves of the water circuit are completely open.
Check if the water filter needs cleaning.
Make sure there is no air in the system (purge air).
Check on the manometer that there is sufficient water pressure. The water pressure must be>1
bar (water is cold).
Make sure that the expansion vessel is not broken.
Check that the resistance in the water circuit is not too high for the pump.
The water volume in the
installation is too low.
Make sure that the water volume in the installation is above the minimum required value (refer to
WATER CONNECTIONS - Checking the water volume and expansion vessel pre-pressure").
This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be carried out by your local technician.
Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as
loose connections or defective wiring.
Содержание WSAN-YMi 101
Страница 1: ......
Страница 18: ......
Страница 35: ...Type 2 Type 2 Type 2 Type 2...
Страница 42: ...T4 Outdoor Temperatures T1S set water temperature It is curve number 9 It can be set as shown in the figure...
Страница 43: ...T4 Outdoor Temperatures T1S set water temperature It is curve number 9 It can be set as shown in the figure...
Страница 84: ...Access by pwd is reserved to qualified personnel The parameters changes may cause malfunctions...
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 127: ......
Страница 128: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...