M07J40G8-00
21/07/08
page 46
TECHNICAL DATA
Acoustic configuration: Standard (ST) / Compressors insulation (SC)
Size
2.160 2.180 2.190 2.200 2.240 2.280 2.300 2.320 2.340
2.360
2.440 2.480 2.540 2.600
COOLING
Cooling capacity
1 kW
400
456
505
556
616
699
767
835
882
935
1016
1138
1272
1411
Compressor power input
kW
112
129
142
159
175
202
224
245
258
274
295
333
369
413
Total power input
2 kW
129
146
162
179
198
225
247
268
284
300
328
366
408
452
Heating capacity total recovery
kW
514
586
637
701
775
872
953
1027
1074
1155
1258
1404
1574
1732
Heating capacity partial recovery
kW
102
117
129
143
158
180
198
216
228
242
262
294
328
365
EER
3.1
3.12
3.12
3.11
3.11
3.11
3.11
3.12
3.11
3.12
3.1
3.11
3.12
3.12
ESEER
3.55
3.45
3.61
3.65
3.64
3.72
3.72
3.79
3.79
3.83
3.67
3.74
3.73
3.77
COMPRESSOR
Type of compressors
3
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
DSW
No. of Compressors
Nr
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Std Capacity control steps
Nr
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
STEPLESS
Refrigerant circuits
Nr
2
2
2
2
2
2
2
2
2
2
2
2
2
2
INTERNAL EXCHANGER
Type of internal exchanger
4
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
S&T
No. of internal exchangers
Nr
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Water flow rate (Internal
Exchanger)
l/s
19.1
21.8
24.1
26.6
29.4
33.4
36.6
39.9
42.1
44.7
48.5
54.4
60.8
67.4
internal exchanger pressure drop
kPa
59
56
75
76
67
56
73
84
73
76
53
69
83
107
Water content
l
164.4
159.3
152.7
263.3
255.7
248.3
241.2
241.2
233.3
409.6
400.9
391.9
461.8
451.4
EXTERNAL SECTION FANS
Type of fans
5
AX
AX
AX
AX
AX
AX
AX
AX
AX
AX
AX
AX
AX
AX
Number of fans
Nr
10
10
12
12
14
14
14
14
16
16
20
20
24
24
Standard air flow
l/s
55480
55480
61250
61250
71730
71730
71730
71730
81340
81340 101540 101540 122500 122500
CONNECTIONS
Water fittings
141.3
141.3
141.3
168.3
168.3
168.3
168.3
168.3
168.3
219.1
219.1
219.1
219.1
219.1
POWER SUPPLY
Standard power supply
V
400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
(1) data referred to the following conditions :
internal exchanger water = 12/7°C
external exchanger air intake 35°C
(2) According to EUROVENT the Total Power Input does not consider the pump share, required to overcome the pressure drop for the solution circulation
inside the exchangers.
(3) DSW = twin-screw compressor
(4) S&T = tube bundle
(5) AX = axial-flow fan