WATER CONNECTIONS

 

 

GENERAL 

Piping must be designed with the least possible number of 
bends  and  head  variations.  If  the  pressure  chute  of  the 
installation is above the useful prevalence of the pump, the 
water  delivery  capacity  is  reduced  as  well  as,  as  a 
consequence, the thermal exchange and the yield.  

INTERCEPTING VALVES 

Install  on  the  input  and  output  of  the  user  parts 
(exchangers,  coils,  humidifiers,  etc)  So  that  it  will  be 
possible to carry out all the service operations and possible 
substitutions without emptying the installation. 

PRESSURE AND TEMPERATURE INDICATOR 

Install  on  the  input  and  output  of  the  user  parts 
(exchangers,  coils,  humidifiers,  etc)  So  that  it  will  be 
possible to carry out all the service operations. 

AUTOMATIC OR MANUAL ESCAPE VALVES 

Install the highest points of tubes in a way that the air can 
escape form the circuit.  

BLEEDING COCK 

Install them at the lowest points of the circuit, so as to allow 
emptying. 

LEAKAGE TESTS 

Before performing the insulation of the tubes, carry out a 
leakage test. 

TUBE INSULATION  

All  tubes  of  water  must  be  insulated  so  that  to  avoid  the 
formation  of  condensation  and  thermal  dispersions  along 
the  tubes  themselves.  Verify  that  the  insulation  is  the 
vapour coil type. The connections for the air escape and for 
the  emptying  must  be  out  of  the  insulating  thickness  to 
assure the accessibility. 
 
 
 

 

CONNECTIONS SUPPORTS 

The weight of the hydraulic connections must be supported 
in the exterior of the unit so as not to stress the connections 
of user devices (exchangers, coils, humidifiers, etc ) . 

ANTI-VIBRATION DEVICES 

In case of units with anti-vibration devices, it is necessary to 
assemble elastic joints, even on water connections. 

RISK OF FREEZE 

If the unit and the relevant water connections are subject to 
temperatures near 0°C:  

• 

mix the water of the system with glycol 

• 

protect the tubes with heating cables under the tubes 
insulation 

• 

empty the system by verifying that: 

no taps are closed so they can not trap the water, 
even after emptying 

there are no low points where the water can 
stagnate even after emptying; blow if necessary 

INSTALLATION EMPTYING  

The refilling of the water present in the installation increase 
the oxidation phenomena and lime deposits.  
If necessary empty only the interested system section and 
anyway empty or refill the installation if necessary .  

EXPANSION TANK 

The installation must be kept at the right pressure by both 
an  expansion  tank  and  a  combined  valve  of  pressure 
reduction and discharge; if the components are present on 
the  unit,  they  must  be  installed  on  the  installation.  The 
expansion  tank  must  be  dimensioned  in  function  of  the 
water in the installation. 
ARIES EFFECTS AND AIR BUBBLES CAN PRODUCE 
THE OVERCOMING AND CAUSE WATER DROPS.

 

 

EXCHANGER USE SIDE 

 

FILTER 

It is very important for the water to be free of impurities. If it 
is not, the efficiency of thermal exchange is diminished. In 
worst cases, the exchanger can be irreparably damaged. If 
the  filter  is  not  present  on  the  machine,  it  must  be 
immediately  installed  upstream  from  the  unit,  in  a  position 
which can be easily reached for cleaning. 
The filter mesh must be :  

• 

< 1 mm unit with 1 compressor 

• 

< 1.5 mm multicompressor unit. 

FLOW SWITCH 

The  flow  switch  must  be  present  as  a  component  of  the 
system, so as to ensure shutdown of the unit if water is not 
circulating.  It  must  be  installed  in  a  straight  tract  of  the 
tubes,  not  near  the  elbows,  which  can  generate  harmful 
turbulence. 

UNFREEZABLE LIQUIDS 

If the unit is used when the water temperature is lower than 
+  4°C,  avoid  the  formation  of  ice  by  using  unfreezable 
liquids  (ex.  Ethilenic  Glycol)  in  the  necessary  percentage. 
The use must also be determined for ambient temperatures 
near 0°C . 

ANTIFREEZE RESISTANCES  

If  the  unit  is  equipped  with  antifreeze  resistances  on  the 
exchanger  side  (standard  or  optional  according  to  the 
models),  verify  that  they  are  electrically  fed  during  periods 
that the machine is stopped (night, weekends, long stops) 

WASHING THE SYSTEM 

Carefully  wash  the  system  by  using  clean  water  and 
discharge it before connecting the unit. 

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Содержание 2.160

Страница 1: ...0 2 180 2 190 2 200 2 240 2 280 2 300 2 320 2 340 2 360 2 440 2 480 2 540 2 600 AIR COOLED WATER CHILLER FOR OUTDOOR INSTALLATION Installation and Use Manual M07J40G8 00 21 07 08 http splitoff ru tehn...

Страница 2: ...http splitoff ru tehn doc html...

Страница 3: ...M COMPOSITION 18 MODBUS CONVERTER CAN to MODBUS via RS 485 19 S T A R T U P 2 1 PRELIMINARY CHECKS 21 REFRIGERANT SYSTEM 21 WATER SYSTEM 21 ELECTRICAL SYSTEM 21 VERIFy tensions absorptions 22 UNIT EQU...

Страница 4: ...provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is not possible to i...

Страница 5: ...espect the instructions given in this manual will cause the warranty to lapse INTENDED USE The unit must only be used for the specific purpose it was designed The unit is designed to cool water or a w...

Страница 6: ...AL RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself Isolate the unit...

Страница 7: ...in toxic and corrosive products 04 First aid measures Inhalation Carry the victim into the open air Resort to oxygen or artificial respiration if necessary Contact with skin Frostbite must be treated...

Страница 8: ...ments conducted on animals rabbits Contact with the eyes practically non irritating for eyes in experiments conducted on animals rabbits Sensibilisation Contact with skin Experim ental for the animal...

Страница 9: ...tical points during handling stairs flights disconnected routes doors etc Verify that the lifting capacity of the means used is adequate to the unit weight Consider that the barycentre could be moved...

Страница 10: ...be reached by snow 6 Verify that the fixing supporting points are level and suitable to support the weight of the unit see the weight and the weights distribution 7 It is recommended to put the unit o...

Страница 11: ...vide windbreaks in locations with strong winds INSTALLATION OF ANTIVIBRATION MOUNTS MINIMUM DIMENSIONS SUGGESTED CONCRETE FOUNDATION JACK PLATE UNLOADED HEIGHT CLAMPS DROWNED IN TH CONCRETE NOT SUPPLI...

Страница 12: ...o taps are closed so they can not trap the water even after emptying o there are no low points where the water can stagnate even after emptying blow if necessary INSTALLATION EMPTYING The refilling of...

Страница 13: ...e RECOVERY EXCHANGER OPTIONAL OPTIONAL The unit can be equipped with exchangers to allow the recovery TOTAL with 100 recovery of the condensation heat the thermoregulation is performed by CLIVET contr...

Страница 14: ...stems where this would be called for By equipping the refrigerating units with the Hydropack accessory the necessary flow capacity head are provided in different versions HYDROPACK with 2 pumps Per le...

Страница 15: ...a different tension and that are able to emit electromagnetic disturbances Do not lay the cable near devices which can generate electromagnetic interferences Do not lay the cables parallel to other ca...

Страница 16: ...d etc so with ON or OFF periods relatively longs some hours It has not to be used with ON or OFF cycles too much shorts they compromise the operating logic and they can cause malfunctions or faults In...

Страница 17: ...essary MENU NUM Parameter name meaning 4 MaxCExtC Max Summer correction value 110 HexMinC Min correction ext enthalpy parameters thermoregulation compext 111 HexMaxC MAX correction ext enthalpy parame...

Страница 18: ...ooling circuit compressors fans valves and relative safety devices 21 20 19 18 17 16 15 14 13 12 DRIVER VCM 1 2 3 4 5 6 7 8 9 10 11 12 ELECTRONIC THERMOSTATIC EXPANSION VALVE MODULE code C5110802 This...

Страница 19: ...XC 12 12 A L H QE unit 1 GND C5110675 L SHILD H 230 1 50 2 X 0 34 mm2 sch CAN to CAN Can 0 Can 1 MODBUS CONVERTER CAN TO MODBUS VIA RS 485 Interfacing via RS 485 is performed using a converter for ea...

Страница 20: ...r information about cables for the Lonworks network visit the web site www echelon com LONWORKS technology is a complete platform to implement the network system control These networks consist of inte...

Страница 21: ...quired bleed it using the vent valves in the system Check that there are no ARIES EFFECTS in the transient pump and or valve activation deactivation When using antifreeze solutions make sure the glyco...

Страница 22: ...ons in the ELECTRIC WIRING chapter SETTING THE SET POINT Check if it is necessary to modify the set points shown in the CONTROL chapter EVAPORATOR WATER FLOW RATE Check that the difference between the...

Страница 23: ...value is both negative and positive the shorter the interval among the scanning points will be The value of the scanning time is displayed at the status 6 when the status 7 has reached the value of t...

Страница 24: ...pump tests the water temperature and even activates one or more compressors It is necessary to modify the parameters with access reserved to the assistance centres MENU NUM Parameter name meaning 25...

Страница 25: ...oint 12 118 CEN SetCool Cooling Set Point 6 5 272 CEN SetRecovery NOT USED 35 menu PARAMETERS THERMOREG MAINTENANCE 114 CEN SetMantCool Summer maintenance setpoint 15 menu PARAMETERS THERMOREG ANTIFRE...

Страница 26: ...les timing bands CLOCK SETUP Set the clock ID Tast Cen ATC ONLY PASSWORD ATC ONLY To go back to the main menu ESC I HOME button HOME To enter in the SETUP menu ESC I HOME button F3 SETUP To select the...

Страница 27: ...de ESC I HOME button F4 To select Setpoint ESC I HOME buttons F1 F2 Set the manual setpoint of the event ESC I HOME buttons F3 F4 SETUP SCHEDULING EnSCHEDULING enables disables timing bands CONFIGURE...

Страница 28: ...ST Unit_2 Mod_comp1 LIST Mod_comp2 LIST Mod_comp3 LIST Mod_Evap LIST example Visualized stata referring to UNIT 1 COMP 2 MODULE To enter in the STATA menu ESC I HOME button F4 STATE To select the modu...

Страница 29: ...71 BitMap connected nodes MS bit map of a byte 72 Hours pump 1 PMP 73 Hours pump 2 PMP 74 Hours pump 3 PMP Index UNIT_1 MOD COMP_1 Stata UM 29 Compressor 1 1 ON 0 OFF 30 Compressor 2 1 ON 0 OFF 31 Co...

Страница 30: ...lly dangerous situation for the machine integrity An immediate analysis is necessary to detect the causes of the block A repeated reset can provoke irreversible damage That is why reset is MANUAL PRE...

Страница 31: ...r Reset input fault 4 E005 Outside RH probe fault 5 E006 Thermal cut out alarm pump 1 on control module 6 E007 Thermal cut out alarm pump 2 on control module 7 E008 Flow switch alarm on control module...

Страница 32: ...25 max TS TEE prealarm 66 E126 max TS TEE prealarm 67 E127 power fail alarm 68 E128 stepper motor error alarm PUMP MODULE Str Name 53 E501 Water flow probe fault 54 E502 Thermal pump 1alarm Pump Modul...

Страница 33: ...t the fans and the relative protection gridsare well fixed Check if possible the unbalances of the electro fan evident by noise and anomalous vibrations Verify that the terminal protection covers are...

Страница 34: ...to local actuation norms In Italy refer to the Ministerial Decree of 1st December 2004 no 329 and following modifications which defines the performances to be executed the units of 1st category and th...

Страница 35: ...71 5 8 25 73 10 8 45 66 15 8 59 96 20 8 71 32 25 8 80 83 30 8 89 03 35 8 96 21 1 0 10 08 6 0 26 71 11 0 46 32 16 0 60 46 21 0 71 73 26 0 81 18 31 0 89 33 36 0 96 48 1 2 7 64 6 2 27 67 11 2 46 96 16 2...

Страница 36: ...rature see operating limits 2 low water temperature see operating limits 3 insufficient water flow to the exchanger high thermal difference between input and output 4 not CONSTANT flow for example if...

Страница 37: ...refrigerant charge FAN PROTECTION 1 Identify the part on the wiring diagram 2 fan mechanically jammed bearings drive belt if present 3 Loose electric contacts terminals leads broken 4 electrical wind...

Страница 38: ...in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dismantling and dis...

Страница 39: ...M07J40G8 00 21 07 08 page 39 TECHNICAL DATA http splitoff ru tehn doc html...

Страница 40: ...63 1370 1446 1504 1363 1399 W2 kg 1191 1198 1258 1342 1285 1291 1351 1435 1285 1320 W3 kg 1090 1094 1159 1242 1137 1140 1206 1289 1137 1169 W4 kg 1003 1007 1057 1166 1058 1062 1111 1220 1058 1091 Oper...

Страница 41: ...748 752 825 830 797 845 866 870 W4 kg 699 699 703 703 708 725 742 742 W5 kg 1030 1034 1085 1088 954 1106 1125 1128 W6 kg 640 641 661 663 613 683 701 702 Operating weight kg 5138 5160 5504 5526 5233 56...

Страница 42: ...ting weight kg 5520 5902 5870 6222 Shipping weight kg 5279 5661 5629 5981 Particular accessories executions or versions can bring about a great variation of the mass represented here Please contact ou...

Страница 43: ...88 912 913 W5 kg 1237 1491 1292 1599 1259 1304 W6 kg 813 894 859 879 785 876 Operating weight kg 6249 6730 6669 7150 6366 6760 Shipping weight kg 6016 6321 6436 6741 6125 6519 Particular accessories e...

Страница 44: ...866 966 899 912 808 816 857 W6 kg 1441 1503 1455 1390 1066 1329 1366 W7 kg 645 733 669 692 605 607 646 W8 kg 607 680 629 643 570 572 610 Operating weight kg 7394 8392 7814 8812 7362 7731 8112 Shipping...

Страница 45: ...g 1041 1048 953 1047 1058 1048 W6 kg 1658 1513 1543 1539 1324 1532 W7 kg 813 829 741 825 742 826 W8 kg 736 677 702 707 701 702 Operating weight kg 9253 9687 9595 10029 9418 9967 Shipping weight kg 879...

Страница 46: ...XCHANGER Type of internal exchanger 4 S T S T S T S T S T S T S T S T S T S T S T S T S T S T No of internal exchangers Nr 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Water flow rate Internal Exchanger l s 19 1 21 8...

Страница 47: ...al exchanger 4 S T S T S T S T S T S T S T S T S T S T S T S T S T No of internal exchangers Nr 1 1 1 1 1 1 1 1 1 1 1 1 1 Water flow rate Internal Exchanger l s 19 1 21 7 24 2 26 4 29 3 33 2 36 7 39 6...

Страница 48: ...d Version external exchanger air intake 35 C 9 Low temperature version external exchanger air intake 35 C Fluid with ethylene glycol of 40 Acoustic configuration Low noise LN Size 2 160 2 180 2 190 2...

Страница 49: ...NS ethylene glycol by weight 5 10 15 20 25 30 35 40 Freezing temperature C 2 0 3 9 6 5 8 9 11 8 15 6 19 0 23 4 Safety temperature C 3 0 1 0 1 0 4 0 6 0 10 0 14 0 19 0 Cooling Capacity Factor Nr 0 995...

Страница 50: ...2 190 90 94 100 93 90 86 78 75 75 96 2 200 91 94 101 93 89 86 79 77 75 96 2 240 91 94 101 93 90 86 79 77 75 96 2 280 91 95 101 94 90 86 80 78 76 97 2 300 91 94 100 96 90 88 81 78 76 91 2 320 90 92 98...

Страница 51: ...nl CLIVET TFAIRSYSTEMS P LTD Malur INDIA Tel 91 8151 232683 5 Fax 91 8151 232684 info clivettfa com CLIVET SPA BUREAUDE LIAISON EN FRANCE Verrier s le Buisson FRANCE Tel 33 0 1 69 20 25 75 Fax 33 0 1...

Отзывы: