M07J40G8-00
21/07/08
page 17
MENU
NUM
Parameter name
meaning
1
EnCompExt
External compensation enabling
0 = no; 1 = COOL only; 2 = HEAT only; 3 = always
4
MaxCExtC
Max. ext. compensation value of cooling
106
CextMaxC
Max. ext. temp. of cooling compensation
parameter
control
compext
107
CextMinC
Min. ext. temp. of cooling compensation
parameter-set-sensors
9
ProbeText
It enables ext. temp. probe: 0=yes ; 1=no
SUMMER
p4
p106
p107
Text °C
set COMPENSATO
EXTERNAL AIR HUMIDITY PROBE - Optional
It allows the automatic correction of the set-point, according to external air enthalpy .
Nel funzionamento invernale la correzione avviene sulla sola temperatura.
The working process is similar to the above mentioned process . The parameter configuration is necessary.
MENU
NUM
Parameter name
meaning
4
MaxCExtC
Max. Summer correction value
110
HexMinC
Min. correction ext. enthalpy
parameters
thermoregulation
compext
111
HexMaxC
MAX. correction ext. enthalpy
parameter-set-sensors
23
ProbeURExt
Enables external humidity probe: 1=YES / 0=NO
WATER RESET - Opzionale
It allows the automatic correction of the set-point, according to an external signal of 4-20 mA or 0-10 vcc.
The working process is similar to the above mentioned process .
The parameter configuration is necessary.
MENU
NUM
Parameter name
meaning
11
MaxCWRC
WR Summer correction max. value
75
WaterReset
Water Reset enabling:
0 = no; 1 = COOL only; 2 = HEAT only; 3 = always
105
SWRMaxC
Summer MAX correction signal
parameter
control
waterreset
108
SWRMinC
Summer MIN correction signal
parameter-set-sensors
83
TypeWR
Inlet signal type: 0=0-10V; 1=4-20mA
SUMMER
°C
set point COMPENSATO
par 108
par 105
4 mA
20 mA
par11