OPERATING LIMITS (COOLING)
Acoustic configuration: Standard (ST) / Compressors insulation (SC)
Size
2.160 2.180 2.190 2.200 2.240 2.280 2.300 2.320 2.340 2.360 2.440 2.480 2.540 2.600
EXTERNAL EXCHANGER
Max air intake temperature
1
°C
48
47
46
46
46
46
46
46
46
46
46
46
46
46
Max air intake temperature
2
°C
53
52
51
51
51
51
51
51
51
51
51
51
51
51
Min. air intake temperature
3
°C
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
Min. air intake temperature
4
°C
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
Min. air intake temperature
5
°C
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Min. air intake temperature
6
°C
11
11
11
11
11
11
11
11
11
11
11
11
11
11
INTERNAL EXCHANGER
Max water inlet temperature
7
°C
21
21
21
21
21
21
21
21
21
21
21
21
21
21
Min. water outlet temperature
8
°C
5
5
5
5
5
5
5
5
5
5
5
5
5
5
Min. water outlet temperature
9
°C
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
(1) unit at full load: internal exchanger water 12/7°C
(2) capacity-controlled unit (automatic capacity control)
(3) unit at full load
external exchanger air in quiet
(4) capacity-controlled unit (automatic capacity control)
external exchanger air in quiet
(5) capacity-controlled unit (automatic capacity control)
air to external exchanger = 0.5m/sec
(6) capacity-controlled unit (automatic capacity control)
external exchanger air = 1m/sec
(7) external exchanger air intake 35°C
(8) Standard Version
external exchanger air intake 35°C
(9) Low temperature version
external exchanger air intake 35°C
Fluid with ethylene glycol of 40%
Acoustic configuration: Low noise (LN)
Size
2.160 2.180
2.190
2.200
2.240
2.280
2.300
2.320
2.340
2.360 2.440
2.480
2.540
EXTERNAL EXCHANGER
Max air intake temperature
1
°C
46
46
46
46
45
45
44
44
44
44
44
44
44
Max air intake temperature
2
°C
51
51
51
51
50
50
49
49
49
49
49
49
49
Min. air intake temperature
3
°C
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
-10
Min. air intake temperature
4
°C
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
-7
Min. air intake temperature
5
°C
2
2
2
2
2
2
2
2
2
2
2
2
2
Min. air intake temperature
6
°C
11
11
11
11
11
11
11
11
11
11
11
11
11
INTERNAL EXCHANGER
Max water inlet temperature
7
°C
21
21
21
21
21
21
21
21
21
21
21
21
21
Min. water outlet temperature
8
°C
5
5
5
5
5
5
5
5
5
5
5
5
5
Min. water outlet temperature
9
°C
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
-8
(1) unit at full load: internal exchanger water 12/7°C
(2) capacity-controlled unit (automatic capacity control)
(3) unit at full load
external exchanger air in quiet
(4) capacity-controlled unit (automatic capacity control)
external exchanger air in quiet
(5) capacity-controlled unit (automatic capacity control)
air to external exchanger = 0.5m/sec
(6) capacity-controlled unit (automatic capacity control)
external exchanger air = 1m/sec
(7) external exchanger air intake 35°C
(8) Standard Version
external exchanger air intake 35°C
(9) Low temperature version
external exchanger air intake 35°C
Fluid with ethylene glycol of 40%