UNIT NETWORK – MINI NETWORK – MASTER SLAVE
The
CLIVET TALK
Local Network
system allows to connect up to 6 machines in a network which all serve the same
installation. To interact with the network which controls the working of the system, it is necessary to have a CAN to CAN
converter code C5110692 for each machine.
Each single machine is equipped with the standard electronic devices: if necessary, it can function as an independent
unit.
SpinChiller
SpinChiller
SpinChiller
CAN 0
At use
Cavo CAN OPEN
Max. extension 200mt with a twisted and shielded pair
L max. single
derivation =20cm
L max. single
derivation =20cm
L max. single
derivation =20cm
Unit #3
Unit #2
Unit #1
Water Reset
Temp. Ext
UR% Ext
Mode remoto
PE1W0009
(C5110692)
Master #1
PE1W0009
(C5110692)
Slave #2
PE1W0009
(C5110692)
Slave #3
Unit MASTER
CAN 1
CAN 0
CAN 1
CAN 0
CAN 1
CONNECTION CABLE :
Section (nominal)
0.34mm2
Heater
70m
Ω
/meter
Impedance 120m
Ω
/meter
Propagation delay 5nS/metrer
Length MAX
200meters
DATALOGGER cod PE1W0006
CONNECTIONS : make reference to the electrical panel and to SIGNALS/DATA LINES paragraph
KIT LONWORKS
Upon request, the unit is equipped with the kit already mounted on the electric board; it can eventually be mounted later.
Refer to the electric diagram and to the LONWORKS MANUAL.
For information about cables for the Lonworks network, visit the web site
www.echelon.com
.
L
ON
W
ORKS
technology is a complete platform to implement the network system control. These networks consist of intelligent control
instruments, or
nodes,
which interact with their environment and communicate to each other by using a common message based on
the (
LonTalk®
) protocol. A L
ON
W
ORKS
network can have up to 32,385 nodes subdivided into 255 sub-networks (127 nodes/sub-
network).
The Gateway device is already configured, according to the Echelon classification for the type of the unit it is designed for, with a
number of managed variables, which is a sub-array of those managed originally by the machine and able to accept the Echelon
standard profiles. The supply of this device does not include the activity of configuration and management of the LonWorks network to
which it is connected; as usual, they are supplied by the Supervision System supplier.
Signalization led of gateway in
programming
Dip switch for setting the module
serial address
Signalization led of gateway
operation
jumper to activate the gateway
firmware rewriting
terminator INSERTED
Dip switch configuration of CAN
OPEN addresses
Terminator NOT ACTIVATED
17 18 19 20 21 22 23 24
1
2 3 4
LiteConnector
LonWorks
Module Status
Serial Status
Service
Ne
t
B
Ne
t
A
Ne
t
B
Ne
t
A
SH
LD
NC
GN
D
Vi
n+
RS485
C5110676
Lon Works SIDE
1
8
ON
1
O
N
12 Vac
485
+
-
S
L
G
H
CAN 0
GATEWAY LON-WORKS
CAN TO MODBUS
12 Vac
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html