M07J40G8-00
21/07/08
page 29
Index
GENERAL stata
UM
0
Machine status
1=ON / 0=OFF
1
Machine mode
0=Cool, 1= Heat
2
Actual set point
°C ( tenths )
3
Inlet temperature
°C (tenths)
4
Outlet temperature
°C (tenths)
5
Number of steps activated
6
Current step value (compensations)
°C (tenths)
7
Step activation timer
sec
8
Step activation dynamic TimeScan
sec
9
CompExt
°C (tenths)
10
CompWR
°C (tenths)
11
CompCar
°C (tenths)
12
CompSpunti
°C (tenths)
13
CompDuty
°C (tenths)
14
Ambient temperature
°C (tenths)
15
Ambient humidity
%
16
Free Cooling valve percentage
%
17
Free Cooling flow percentage
%
18
Free Cooling valve control
1=ON / 0=OFF
19
Pump 1 status
1=ON / 0=OFF
20
Pump 2 status
1=ON / 0=OFF
21
Water Reset
%
22
Demand Limit
%
60
Digital input
bit map of a byte
68
Water flow analogic out
69
Pump module digital out
bit map of a byte
71
BitMap connected nodes MS
bit map of a byte
72
Hours pump 1 PMP
73
Hours pump 2 PMP
74
Hours pump 3 PMP
Index
UNIT_1 – MOD COMP_1 Stata
UM
29
Compressor 1
1=ON / 0=OFF
30
Compressor 2
1=ON / 0=OFF
31
Compressor 3
1=ON / 0=OFF
32
Cp 1 timer status
1=ON / 0=OFF
33
Cp 2 timer status
1=ON / 0=OFF
34
Cp 3 timer status
1=ON / 0=OFF
35
Valve 1 c1 status
1=ON / 0=OFF
36
Valve 2 c1 status
1=ON / 0=OFF
37
Valve 3 c1 status
1=ON / 0=OFF
38
Valve 1 c2 status
1=ON / 0=OFF
39
Valve 2 c2 status
1=ON / 0=OFF
40
Valve 3 c2 status
1=ON / 0=OFF
41
Valve 1 c3 status
1=ON / 0=OFF
Index
UNIT_1 – MOD COMP_1 Stata
UM
42
Valve 2 c3 status
1=ON / 0=OFF
43
Valve 3 c3 status
1=ON / 0=OFF
44
Liquid solenoid
1=ON / 0=OFF
45
Coil temperature
°C ( tenths)
46
Recovery temperature
°C ( tenths)
47
Condensation pressure
bar
48
Evaporation pressure
bar
49
Fan Status
bar
50
Defrost Status
1=ON / 0=OFF
51
Defrost count time
sec
52
Compressor 1 operating time
53
Comp. 1 starts
54
Compressor 2 operating time
55
Comp. 2 starts