Page 26
Ultra Classic (VT) Series
q
High voltage is correct and matches nameplate
q
Fuses, breakers and wire size correct
q
Low voltage wiring complete
q
Piping completed and water system cleaned and flushed
q
Air is purged from closed loop system
q
Isolation valves are open, water control valves or
loop pumps wired
q
Condensate line open and correctly pitched
q
Transformer switched to lower voltage tap if needed
q
Air coil cleaned
q
HWG pump disconnected unless piping is completed
and air has been purged
q
Blower rotates freely – shipping support has been removed
q
Blower speed correct (taps on correct pins)
q
Air filter is clean and in position
q
Service/access panels are in place
q
Return air temperature is between 40-80°F in
heating and 50-110°F in cooling
q
CXM field selectable options such as thermistor
settings are correct.
BEFORE POWERING UNIT, check the following:
Operating Limits
Environment
– This unit is designed for indoor
installation ONLY.
Power Supply
– A voltage variation of +/– 10% of
nameplate utilization voltage is acceptable.
Starting Conditions
GT-X Units
– Units start and operate in an ambient of
45°F with entering air at 45°F, entering water at 32°F
and both air and water at the stated flow rates of ISO/
ASHRAE/ARI 13256-1 for initial winter start-up.
Notes:
1. These are not normal or continuous operating
conditions. It is assumed that winter start-up
is to bring the building space up to occupancy
temperatures.
2. Voltage utilization range complies with ARI
Standard 110.
UNIT START UP
Ultra Classic
Air Limits
Cooling
Heating
Min. Ambient Air
45°F
45°F
Rated Ambient Air
80°F
70°F
Max. Ambient Air
100°F
85°F
Min. Entering Air
50°F
40°F
Rated Entering Air db/wb
80/67°F
70°F
Max. Entering Air db/wb
110/83°F
80°F
Water Limits
Min. Entering Water
30°F
20°F
Normal Entering Water
50-90°F
30-60°F
Max. Entering Water
110°F
90°F
Table 11: Operating Limit
Determination of operating limits is dependent primarily
upon three factors: 1) return air temperature 2) water
temperature and 3) ambient temperature. When any one of
these factors is at minimum or maximum levels, the other
two factors should be at normal levels to ensure proper
unit operation.
Extreme variations in temperature and humidity
and corrosive water or air will adversely affect unit
performance, reliability and service life.