![ClimateMaster Ultra Classic VT 036 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/climatemaster/ultra-classic-vt-036/ultra-classic-vt-036_installation-operation-and-maintenance-instructions-manual_2624759011.webp)
Ultra Classic (VT) Series
Page 11
Shut-off Valve with Waste
Vent at high point
Cold Inlet
Hot Outlet
to home
Insulated water lines -
5/8” OD 50 ft maximum
Powered
Water
Heater
Upper
element to
120 - 130°F
Lower
element to
100-110°
F
Domestic
Cold Supply
Tee and drain
Shut-off Valve
HOT WATER GENERATOR
The HWG (Hot Water Generator) or desuperheater option
provides considerable operating cost savings by utilizing
excess heat energy from the heat pump to help satisfy
domestic hot water requirements. The HWG is active
throughout the year, providing virtually free hot water
when the heat pump operates in the cooling mode or hot
water at the COP of the heat pump during operation in the
heating mode. Actual HWG water heating capacities are
provided in the appropriate heat pump performance data.
All Climate Master heat pumps equipped with the
HWG option include a built-in water to refrigerant heat
exchanger to eliminate the need to open and tie into the
heat pump’s refrigerant circuit in the field. The control
circuit is also built in. The concentric fitting is optional.
Figure 14 is a typical example of HWG water piping
connections on an UltraClassic unit with a built-in pump.
Using a concentric or coaxial hot water tank connection
fitting eliminates the need to tie into the hot water tank
cold water piping. (see Figure 16)
Typically a single tank of at least 52 gallons is used
to limit installation costs and space. However, a dual
tank, as shown in Figure 15, is the most efficient system
providing the maximum storage and temperate source
water to the desuperheater. Using a concentric hot water
tank connection fitting eliminates the need to tie into
the hot water tank water piping. In high liming areas
(hardness>100ppm or 6 grains per gallon) the alternative
piping scheme in Figure 16 may be used to eliminate the
possible scaling of the smaller cross-sectioned area of
the concentric fitting. It is always advisable to use water
softening equipment on domestic well water systems
to reduce the liming potential and lengthen equipment
life. In extreme water conditions, it may be wise to not
use the HWG option since the probable cost of frequent
maintenance may offset or exceed any savings.
Installation
The HWG aquastat is set at 125 °F and is located on the
HWG heat exchanger “Water In” line. If the HWG is
connected incorrectly or if circulation is reversed, the
aquastat will sense leaving water temperature and prevent
HWG operation. UNDER NO CIRCUMSTANCES
DISCONNECT OR REMOVE THE HWG AQUASTAT!
Full load conditions could drive hot water tank
temperatures far above desirable temperature levels if the
aquastat has been disconnected or removed.
The heat pump, water piping, pump, and hot water tank
should be located where the ambient temperature does not
fall below 50 °F. Keep water piping lengths at a minimum
– DO NOT use a one way length greater than 50 feet.
All installations must be made in accordance with local
codes. The installer is responsible for knowing the local
requirements, and for performing the installation accordingly.
Figure 14: Typical UltraClassic HWG Installation
Содержание Ultra Classic VT 036
Страница 4: ...Page Ultra Classic VT Series Physical Dimensions INSTALLATION...
Страница 18: ...Page 18 Ultra Classic VT Series Electrical Schematic...
Страница 29: ...Ultra Classic VT Series Page 29 Notes...
Страница 30: ...Page 30 Ultra Classic VT Series...