Ultra Classic (VT) Series
Page 17
Accessory Connections
A terminal paralleling the compressor contactor coil
have been provided on the CXM/DXM control of the
UltraClassic line. "A" has been provided to control
accessory devices, such as water valves, electronic air
cleaners, humidifiers, etc.
Note: This terminal should
be used only with 24 Volt signals and not line voltage
signals.
This signal operates with the compressor contactor.
See Figure 21 or the wiring schematic for details.
Figure 21: Accessory Wiring
Figure 22: Well Water AVM Valve Wiring
��������������
�������
�����
�����
�
�
�����
Water Solenoid Valves
When using solenoid valves on ground water installations.
Figure 21 illustrates a typical well water control valve
wiring which will limit wasted water during a lockout
condition. A slow closing valve may be required to
prevent water hammer. When using an AVM -Taco
Slow Closing valves on UltraClassic Series equipment
Figure 20 wiring should be utilized. The valve takes
approximately 60 seconds to open (very little water will
flow before 45 seconds) and it activates the compressor
only after the valve is completely opened (by closing
its end switch). Only relay or triac based electronic
thermostats should be used with the AVM valve. When
wired as shown, the valve will operate properly with the
following notations:
1 - The valve will remain open during a unit lockout.
2 - The valve will draw approximately 25-35 VA through
the “Y” signal of the thermostat.
Note: This can
overheat the anticipators of electromechanical
thermostats.
Therefore only relay or triac based
thermostats should be used.
C
Ultra Classic
C
Thermostat
Y
1
2
3
Y
AVM
Taco Valve
Heater Switch
Thermostat Selection and Wiring
ATA32H01 - Auto Changeover electronic 3 Heat / 2
Cool thermostat
This electronic thermostat, Fig 23, is suited to all Ultra-
Classic applications.
The UltraClassic also employs an ECM board that features:
• Thermostat terminal connections
• Thermostat signal diagnostic LED's
• Airflow selection
• Airflow LED (100 cfm per flash)
• Dehumidification Mode Jumper
Figure 23: ATA32H01 wiring
ELECTRICAL - LOW VOLTAGE
������������������������������
��
��
���
�
�
��
����
�
��
�
��
�
�
�
�
�
��
�
��
����������
��������