![ClimateMaster Ultra Classic VT 036 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/climatemaster/ultra-classic-vt-036/ultra-classic-vt-036_installation-operation-and-maintenance-instructions-manual_2624759023.webp)
Ultra Classic (VT) Series
Page 23
See “Does
not Operate
in Clg”
See “Only
Comp
Runs”
Start
Did Unit
Attempt to
Start?
Did Unit
Lockout at
Start-up?
Unit Short
Cycles?
Only Fan
Runs?
Only
Compressor
Runs?
Did unit lockout
after a period of
operation?
Does unit
operate in
cooling?
Unit is OK!
‘See Performance
Troubleshooting’ for
further help
Check Main
power (see power
problems)
Check fault LED code
on control board
Yes
No
No
No
No
No
Yes
No
Yes
See HP
Fault
See
LP/LOC
Fault
See FP1
Fault
See FP2
Fault
See
Condensate
Fault
See Over/
Under
Voltage
No fault
shown
Replace
CXM
See “Unit
short
cycles”
See “Only
Fan Runs”
No
Yes
Yes
Yes
Yes
CXM Functional
Troubleshooting Chart
Preliminary Trouble Inspection
HAZARDOUS VOLTAGE! DISCONNECT
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING. Failure to disconnect power before
servicing can cause severe personal injury or
death.
TROUBLE ANALYSIS
If operational difficulties are encountered, be sure to
perform the preliminary checks before referring to the
Troubleshooting Chart.
•
Verify that the unit is receiving electrical supply power.
•
Make sure the fuses in the fused disconnect switches
are intact.
After completing the preliminary checks described above,
be sure to inspect for other obvious problems such as
leaking connections, broken or disconnected wires, etc.
If everything appears to be in order, but the unit still fails to
operate properly, refer to the following Troubleshooting Chart.
Troubleshooting Chart
The Troubleshooting Chart that follows is provided to
serve as an aid for identifying malfunctions that may
occur. Within the chart are three columns:
1. The Problem column describes what the unit is doing.
2. The Cause column identifies the most likely sources
of the problem.
3. The Correction column describes what should be
done to correct the problem.
WARNING