ClimateMaster Ultra Classic VT 036 Скачать руководство пользователя страница 14

Page 14   

 

 

 

     Ultra Classic (VT) Series

ECM FAN MOTOR

“fine tune” airflow adjustments. The TEST setting 

runs the ECM motor at 70% torque, which causes 

the motor to operate like a standard PSC motor, and 

disables the CFM counter.

Dehumidification Mode settings: The 

dehumidification mode setting provides field 

selection of humidity control. When operating in 

the normal mode, the cooling airflow settings are 

determined by the cooling tap setting above. When 

dehumidification is enabled there is a reduction in 

airflow in cooling to increase the moisture removal 

of the heat pump. Consult submittal data or 

specifications catalog for the specific unit series and 

model to correlate speed tap to airflow in CFM. The 

dehumidification mode can be enabled in two ways. 

1.  

Constant Dehumidification Mode:

 When the 

dehumidification mode is selected (via DIP 

switch or jumper setting), the ECM motor will 

operate with a multiplier applied to the cooling 

CFM settings (approx. 20-25% lower airflow). 

Any time the unit is running in the cooling mode, 

it will operate at the lower airflow to improve 

latent capacity. The “DEHUM” LED will be 

illuminated at all times. Heating airflow is not 

affected. NOTE: Do not select dehumidification 

mode if cooling setting is tap 1.

2.   Automatic (Humidistat-controlled) 

Dehumidification Mode:

 When the 

dehumidification mode is selected (via DIP 

switch or jumper setting) AND a humidistat 

is connected to terminal DH (version II) or 

HUM (version I), the cooling airflow will only 

be reduced when the humidistat senses that 

additional dehumidification is required. The DH 

(or HUM) terminal is reverse logic. Therefore, a 

humidistat (not dehumidistat) is required. The 

“DEHUM” LED will be illuminated only when the 

humidistat is calling for dehumidification mode. 

Heating airflow is not affected. NOTE: Do not 

select dehumidification mode if cooling setting is 

tap 1.

Fan speeds are selected with jumpers for version 

I or via a nine position DIP switch for version II. To 

take full advantage of the ECM motor features, a 

multi-stage thermostat should be used (2-stage 

heat/2-stage cool or 3-stage heat/2-stage cool).

Note: 

Power must be off to the unit for at least three 

seconds before the ECM motor will recognize a 

speed change. The motor will recognize a change 

in the CFM Adjust or dehumidification mode 

settings while the unit is powered.

There are four different airflow settings from lowest 

airflow rate (speed tap 1) to the highest airflow rate 

(speed tap 4). The charts below indicate settings for 

both versions of the ECM interface board, followed 

by detailed information for each setting.

Cooling

 settings: The cooling setting determines 

the cooling (normal) CFM for all units with ECM 

motor. Cooling (normal) setting is used when the 

unit is not in dehumidification mode. This setting 

also determines the heating CFM for Genesis (GS) 

units. Tap 1 is the lowest CFM setting, while tap 4 is 

the highest CFM setting. To avoid air coil freeze-up, 

tap 1 may not be used if the dehumidification mode 

is selected. Consult submittal data or specifications 

catalog for the specific unit series and model to 

correlate speed tap setting to airflow in CFM. 

Heating

 settings: The heating setting determines 

the heating CFM for Tranquility 27™ (TT) and 

Tranquility 20™ (TS) units. This setting is not used 

for Genesis (GS) units. Tap 1 is the lowest CFM 

setting, while tap 4 is the highest CFM setting. 

Consult submittal data or specifications catalog 

for the specific unit series and model to correlate 

speed tap setting to airflow in CFM.

Auxiliary/Emergency Heat 

settings: The auxiliary/

emergency heat setting determines the CFM when 

the unit is in auxiliary heat or emergency heat 

mode. This setting is used for residential units with 

internal electric heat. When auxiliary electric heat 

is energized (i.e. compressor and electric heat), the 

greater of the auxiliary/emergency or heating setting 

will be used. A “G” (fan) signal must be present from 

the thermostat for electric heat to operate. Consult 

the submittal data or specifications catalog for the 

specific unit series and model to correlate speed tap 

setting to airflow in CFM.

CFM Adjust

 settings:

 The CFM adjust setting 

allows four selections. The NORM setting is the 

factory default position. The + or – settings adjust 

the airflow by +/- 15%. The +/- settings are used to 

Содержание Ultra Classic VT 036

Страница 1: ...Information 22 Troubleshooting Analysis 23 Major Replacement Components 24 Unit Start Up Procedure 26 Operating Limits 26 Pressure Drop Table 28 Operating Pressures 28 Warranty 31 Preventive Maintena...

Страница 2: ...ts have been received Inspect the carton or crating of each unit and inspect each unit for damage Assure the carrier makes proper notation of any shortages or damage on all copies of the freight bill...

Страница 3: ...unit start up read all manuals and become familiar with the unit and its operation Thoroughly check the system before operation Prepare units for installation as follows 1 Compare the electrical data...

Страница 4: ...Page Ultra Classic VT Series Physical Dimensions INSTALLATION...

Страница 5: ...e connector is recommended for both discharge and return air duct connections on metal duct systems Uninsulated duct should be insulated with a minimum of one inch duct insulation Application of the u...

Страница 6: ...essure temperature taps for serviceability run When some sagging in the condensate line may be anticipated as in a long line of plastic pipe or when double trapping may occur Also vent when large unit...

Страница 7: ...re operation Flush the loop with a high volume of water at a high velocity 2 fps in all piping both directions The steps below must be followed for proper flushing Fill loop with water from a garden h...

Страница 8: ...s however your local territory manager should be consulted for the antifreeze best suited to your area Freeze protection should be maintained to 15 F below the lowest expected entering loop temperatur...

Страница 9: ...cal building and zoning department to assure compliance in your area OPEN LOOP WELL WATER SYSTEMS Water Control Valve Note the placement of the water control valve Always maintain water pressure in th...

Страница 10: ...e examined for feasibility before installation City water should not be used as a source in areas where water temperatures fall below 45 F ClimateMaster should be consulted when sizing earth loops for...

Страница 11: ...hown in Figure 15 is the most efficient system providing the maximum storage and temperate source water to the desuperheater Using a concentric hot water tank connection fitting eliminates the need to...

Страница 12: ...eat available from the refrigeration system and con serve the most energy On tanks with both upper and lower elements and thermostats the lower element should be turned down to 100 F or lowest setting...

Страница 13: ...own on the unit serial plate Line and low voltage wiring must be done in accordance with local codes or the National Electric Code whichever is applicable Unit Power Connection Line voltage connection...

Страница 14: ...used 2 stage heat 2 stage cool or 3 stage heat 2 stage cool Note Power must be off to the unit for at least three seconds before the ECM motor will recognize a speed change The motor will recognize a...

Страница 15: ...17B0019N01 DIP Switch Version II Version II 17B0019N01 Version II 17B0019N01 DIP Switch DIP Switch ON OFF DIP Switch Version II 17B0019N01 DIP Switch 17B0019N01 SW9 Table 6 ECM Board Tap Settings Y G...

Страница 16: ...wg hp Setting Stg 2 Stg 1 Fan Stg 2 Stg 1 Fan Setting Mode 4 1290 710 650 1010 550 650 4 1290 036 0 5 1 2 3 1200 660 600 940 520 600 3 1200 2 1110 610 560 870 480 560 2 1110 1 1020 560 510 1 1020 4 1...

Страница 17: ...valve takes approximately 60 seconds to open very little water will flow before 45 seconds and it activates the compressor only after the valve is completely opened by closing its end switch Only rel...

Страница 18: ...Page 18 Ultra Classic VT Series Electrical Schematic...

Страница 19: ...ault For Diagnostic ease at the thermostat the alarm relay will also cycle during test mode The Alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fau...

Страница 20: ...Switch input is bypassed for the initial 60 seconds of a compressor run cycle Low Pressure Lockout Code 3 thermistor temperature must be below the selected freeze protection limit setting for 30 cont...

Страница 21: ...ng Stage 1 mode Y becomes active The first time after power up that there is a call for compressor the compressor will follow a 5 to 80 second random start delay There will also be a 5 min compressor...

Страница 22: ...d at the board connector The thermistor resistance should be measured with the connector removed so that only the impedance of the thermistor is measured If desired this reading can be compared to the...

Страница 23: ...ower before servicing can cause severe personal injury or death TROUBLE ANALYSIS If operational difficulties are encountered be sure to perform the preliminary checks before referring to the Troublesh...

Страница 24: ...cooling Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Air Temperature out of range Too much cold vent air Bring entering air temp within...

Страница 25: ...ng in water heat exchanger Perform Scaling check and clean if necessary X X Inlet Water too Hot or Cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no Air flow...

Страница 26: ...ing Conditions GT X Units Units start and operate in an ambient of 45 F with entering air at 45 F entering water at 32 F and both air and water at the stated flow rates of ISO ASHRAE ARI 13256 1 for i...

Страница 27: ...it pressure drop across the heat exchanger versus the data in Table 12 Heat of rejection can be calculated and compared to specification catalog f Check air temperature drop across the coil when compr...

Страница 28: ...Page 28 Ultra Classic VT Series Table 14 Unit operating pressures and temperatures Table 12 Water Temperature Change Through Heat Exchanger Table 13 Water Pressure Drop Table...

Страница 29: ...Ultra Classic VT Series Page 29 Notes...

Страница 30: ...Page 30 Ultra Classic VT Series...

Страница 31: ...or use of CM s products or 13 Electricity or fuel costs or any increases or unrealized savings in same for any reason whatsoever CM is not responsible for 1 The costs of any fluids refrigerant or sys...

Страница 32: ...t can erode the heat exchanger wall and ultimately produce leaks Filters Filters must be clean to obtain maximum performance They should be inspected every month under normal operating conditions and...

Отзывы: