![ClimateMaster Ultra Classic VT 036 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/climatemaster/ultra-classic-vt-036/ultra-classic-vt-036_installation-operation-and-maintenance-instructions-manual_2624759021.webp)
Ultra Classic (VT) Series
Page 21
Diagnostic Features
The Status LED on the CXM control advises the
serviceman of the current status of the CXM control. The
status LED can display either the current CXM mode or
the last fault memory if in test mode. See Table 8 for a
complete listing of codes.
Unit Operation Description
PowerUp
-
The unit will not operate until all the inputs
and safety controls are checked for normal conditions.
Note: The compressor will have a 5 minute anti-short
cycle delay at power-up.
Standby
-
In Standby mode, Y and W inputs are not active.
Inputs O and G may be active. Compressor will be off.
Cooling
-
To enter Cooling mode, Y and O become
active. The first time after power-up that there is a call for
compressor, the compressor will follow a 5 to 80 second
random start delay. There will also be a 5 min compressor
anti-short cycle protection time as well. After the random start
delay, the compressor relay is energized. On all subsequent
compressor calls, the random start delay is omitted.
Heating Stage 1
-
To enter Heating Stage 1 mode, Y
becomes active. The first time after power-up that there
is a call for compressor, the compressor will follow a 5 to
80 second random start delay. There will also be a 5 min
compressor anti-short cycle protection time as well. After
the random start delay, the compressor relay is energized.
On all subsequent compressor calls, the random start
delay is omitted.
Heating Stage 2
-
To enter Heating Stage 2 mode, W
becomes active (Y already active). The Compressor
relay remains on. EH1 is turned on immediately. With
continuing Heating Stage 2 demand, EH2 will turn on
after 10 minutes. The EH2 will not turn on in heating (or
will turn off if already on) if loop temperature is above
approximately 50°F (FP1 >45°F).
Emergency Heat
-
In Emergency Heat mode, W
becomes active while Y is not active. EH1 is turned on
immediately. With continuing Emergency Heat demand,
EH2 will turn on after 5 minutes. The FP1 and FP2
temperatures do not effect emergency heat operation.
ECM Control Board
The UltraClassic also employs an ECM board that features:
• Thermostat terminal connections
• Thermostat signal diagnostic LED's
• Airflow selection
• Airflow LED (100 cfm per flash)
• Dehumidification Mode Jumper
Table 9: Fault Description Table
�����
���������
����
���������������
��������������������
�
�����������������
��������������������������
�
�������������������������������������������
���������������������������������������������
����������������������������
�
���������������������������������������������
��������������������������������������������
��������������������������������
�
���������������������������������������������
��������������������������������������������
�������������������
�
������������������������������������������
�������
���������������������������
�������������
������������������������������������
CXM CONTROL DESCRIPTION
Содержание Ultra Classic VT 036
Страница 4: ...Page Ultra Classic VT Series Physical Dimensions INSTALLATION...
Страница 18: ...Page 18 Ultra Classic VT Series Electrical Schematic...
Страница 29: ...Ultra Classic VT Series Page 29 Notes...
Страница 30: ...Page 30 Ultra Classic VT Series...