Chapter 3 — Commissioning
3-8
Part No. 750-386
Recirculation Valve
• Discrete Output Valve Control.
• Recirc valve open/close signal based on header pressure.
Auxiliary Analog Inputs
• 4 user configurable analog inputs.
• 1 input required if tray temperature is monitored.
• 1 input required if tray pressure is monitored.
Digital Input Present – Slot 5
• Required for Tank High/Low discrete level switches.
• VFD Bypass.
• One Pump per Boiler.
• If Slot 6 or Slot 7 is present.
Remote Set Point/Lead Lag Order by Comms
• Use Ethernet communications to change (write) lead lag pump
order or header pressure set point (VFD must be selected)
• Requires Communication Watchdog.
• Not available on one pump per boiler applications
English/Metric Unit Display
Not “on the fly” - analog values do NOT automatically rescale.
3.6-System Configuration Screen 2 - Dual Tank
Steam PRV
• Tank Pressure PID Control.
• If selected, Overflow Valve Control not available.
• Reverse Acting selection available.
Overflow Valve
• Linear Analog Overflow Valve Control.
• If selected, PRV Valve Control not available.
Figure 3-8 System Conffig 2 - Dual Tank
Содержание ADAC 1000
Страница 1: ...750 386 05 2017 ADAC 1000 Deaerator Control Operation Manual...
Страница 11: ...www cleaverbrooks com Chapter 2 System Components Components 2 2 Control Panel 2 7 Optional Accessories 2 9...
Страница 22: ...Chapter 2 System Components 2 12 Part No 750 386...
Страница 87: ...www cleaverbrooks com Chapter 5 Input Output Lists Single Tank PLC I O Layout 5 2 Two Tank PLC I O Layout 5 4...
Страница 92: ...Chapter 5 Input Output Lists 5 6 Part No 750 386...
Страница 93: ...www cleaverbrooks com Chapter 6 Parts Parts List 6 2...
Страница 120: ...A 26 Part No 750 386...
Страница 128: ...APPENDIX B ADAC 1000 ProtoNode Tags B 8 Part No 750 386...
Страница 132: ...APPENDIX C Loading a PLC Program C 4 Part No 750 386...
Страница 133: ...APPENDIX D Deaerator Reference Drawings Part No 750 386 D 1 APPENDIX D Deaerator Reference Drawings Water Levels...
Страница 136: ...APPENDIX D Deaerator Reference Drawings D 4 Part No 750 386 Major Components DA with ADAC typical...
Страница 137: ...APPENDIX D Deaerator Reference Drawings Part No 750 386 D 5 Major Components Surge Tank with ADAC typical...
Страница 138: ...APPENDIX D Deaerator Reference Drawings D 6 Part No 750 386 Duo Tank Components typical...
Страница 139: ......
Страница 140: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...