T H E C O N T I N U O U S P O W E R C O M P A N Y
Page 37
From the “Options” menu, click on the “Set value” tab for “4> Opt_Traffic.
1) This option used in the “Standby Mode”.
a. The “Long return always” is used to force a break in power for 2.5 seconds after the
utility power returns. This is used in intersections when a hard-restart needs to be
applied to various devices.
b. The “Short return”(which is the default) is used when no break in the power is needed.
2) This option is used in the “Continuous Operating Mode”.
a. The “Long return if flash volt or minutes trigger occurred” is used to force a break in
power for 2.5 seconds after the utility power returns if “Flash trigger” in minutes or volts
occurs.
b. The “Short return” (which is the default) is used when no break in the power is needed.
3) a. The “Signal port pin 2 carries Flash Timeout Trigger” enables the “Timed Delayed Flash”
feature. This feature enables you to activate the Timer NO\NC contacts on
the
PIM30.
b. The “Signal port pin 2 carries Utility Fail indication” disables the “Timer Delayed
Flash” feature. The Timer NO\NC contacts on the PIM become active when utility
Power is lost.