Chapter 4 Operation Using ICIM
102
78-4025693-01 Rev D
Adjusting Alarm Thresholds
To Adjust Alarm Thresholds
Relative alarm thresholds are both displayed and stored as relative values. This
method for adjusting alarm thresholds lets you choose any valid increment size and
adjust the alarm threshold to any valid value.
You can use the ICIM to change the adjustable alarm thresholds of this module from
their factory default values.
1
At the MODULE
menu, press the
key. The STATUS menu appears on the
ICIM LCD.
2
Press the
key. The alarm thresholds previously set are displayed. If the
label
n/a
is displayed, you cannot configure that alarm threshold. Press the
key to highlight the alarm threshold for the next parameter.
3
When the threshold that you wish to set is highlighted, press the
key.
4
Press the
key or the
key to change the increment size.
5
Press the
key or the
key to adjust the alarm threshold.
Note:
Press the Cancel (
) key to return to the previous menu.
6
Press the
key to save the changes. The message
Data Saved
appears on the
ICIM LCD.
7
When finished, press the
key to return to the MAIN menu.
Содержание Prisma II
Страница 1: ...78 4025693 01 Rev D Prisma II Hybrid Amplifier Installation Guide ...
Страница 2: ......
Страница 10: ......
Страница 20: ......
Страница 26: ......
Страница 54: ......
Страница 56: ...Chapter 3 Operation Using CLI 30 78 4025693 01 Rev D Prisma II Platform Configuration ...
Страница 150: ......
Страница 156: ......
Страница 164: ...Appendix A Prisma II Permitted CLI Commands 138 78 4025693 01 Rev D Reserved for future use ...
Страница 174: ......
Страница 180: ......