7�4�- OPERATING LIMITS
Note:
This screen is not visible on the
“slave”
devices.
In this screen,
, the operating limits of the device are configured:
Figure 61: Configuration screen: Operating limits�
●
Min current
The minimum load current to start the static generator is configured with this parameter. Minimum
current feature is used to increase the system efficiency, by stopping the static generator when re-
quired. The
SVGm
will stop when the load current is below the entered value and will start when it is
higher.
Table 25:Configuration values: Min current�
Min current
Minimum value
0 A
Maximum value
5000 A
●
Current limit
This parameter allows the maximum power of the static generator to be limited. The value is config-
ured as a percentage with respect to the device’s rated power.
Table 26:Configuration values: Current limit�
Current limit
Minimum value
20 %
Maximum value
100 %
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.