77
Instruction Manual
SVGm
Table 41 (Cont�): Modbus memory map: Filter messages (Table 3)�
Parameter
Address
Initial Conditions for which the device
does not start up
(5)
.
108
Bit
Description
0x0400
Maximum load.
0x0800
L1 filter current has exceeded the upper limit.
0x1000
L2 filter current has exceeded the upper limit.
0x2000
L3 filter current has exceeded the upper limit.
0x4000
No communication at slave comms bus.
0x8000
SVGm
cannot generate the expected current waveform.
(5)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
Table 42: Modbus memory map: Static generator messages (Table 4)�
Parameter
Address
SVGm
status
(6)
104
Status (Decimal value)
Description
0
The device is starting the systems.
50
Initiating internal communication systems
60
Configuring the device.
100
The
SVGm
is starting up.
200
Waiting for the conditions to be met in order to operate.
300
Device stopped.
400
The
SVGm
is synchronising with the mains.
500
Charging process of the internal bus prior to start-up.
600
Device is operating.
700
An alarm has been generated.
(6)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
Содержание SVGm
Страница 1: ...SVGm M248B01 03 22A Static var generator INSTRUCTION MANUAL ...
Страница 2: ...2 SVGm Instruction Manual ...
Страница 105: ...105 Instruction Manual SVGm 14 CE CERTIFICATE ...
Страница 106: ...106 SVGm Instruction Manual ...
Страница 107: ...107 Instruction Manual SVGm ...