17
No.
Description
Setting
Default
Display conditions
Read-only (
CONTINUED
)
1
251 Control setpoint
If P141 ≠ 5 and ≠ 6
1
252 Outdoor air temperature
1
255 Water inlet temperature, heat exchanger 1
1
256 Water outlet temperature, heat exchanger 1
1
257 Hot water inlet temp., condenser
If P2 = 1 and P141 = 1
1
258 Hot water outlet temp., condenser
If P2 = 1 and P141 = 3
1
259
Refrigerant temperature, circuit 1 coils
A-B
C-D
If P2 = 3
If P2 = 3 and P14 = 2
If P2 = 3 and P14 = 4
1
260 Refrigerant temperature, heat exchanger 1
If P2 = 1 or 2
1
261 Manifold water outlet temperature
If P6 = 2 - P2 = 1, 2 or 3
1
262 Water outlet temperature, heat exchanger 2
If P6 = 2
1
263
Refrigerant temperature, circuit 2 coils
A-B
C-D
If P2 = 3 and P3 = 2
If P2 = 3 and P3 = 2 and P14 = 2
If P2 = 3 and P3 = 2 and P14 = 4
1
264 Refrigerant temperature, heat exchanger 2
If P2 = 1 or 2 and if P6 = 2
1
265 Exchanger ambient temperature
If P2 = Air-to-water
1
266 Calculated frosting time, circuit 1
If P2 = 3,
1
267 Calculated frosting time, circuit 2
If P2 = 3 and P3 = 2
1
268 Value of reference ΔT for defrosting of circuit 1
If P159 = Optimised
1
269 Value of reference ΔT for defrosting of circuit 2
If P159 = Optimised and P3 = 2
1
285 Runtime in heating mode
If P119 ≠ Cooling
1
286 Runtime in cooling mode
If P119 ≠ Heating
1
287 Pump 1 runtime (in hours)
1
288 Pump 2 runtime (in hours)
If (P2 = 1) or P25 = 2
1
289 No. of times P99 set to "No"
1
290 No. of water flow cut-offs in 1 hour
Visible if (cooling and P2 = 1) or
if P2 = 3 or if P2 = 2 and P25 ≠ 2
Circuit 1
1
300 Circuit 1 HP
1
300.1 Circuit 1 HP control setpoint
If P3 = 1 or 2 and P11 = Intertwined
1
301 Circuit 1 condensation temperature
See appendix
1
302.1 Discharge temperature 1
1
302.2 Discharge temperature 2
If P4 = 2
1
303.1 Desuperheat on discharge 1
P302.1 - P301
1
303.2 Desuperheat on discharge 2
P302.2 - P301
If P4 = 2
1
304 Circuit 1 LP
1
305 Circuit 1 evaporation temperature
See appendix
1
306 Circuit 1 suction temperature
°C
1
307 Circuit 1 superheat
°C
1
308 Number of HP1 cut-offs in 24 hours
1
309 Number of LP1 cut-offs in 24 hours
1
310 Number of starts, stage 1, circuit 1
1
311 Runtime (in hours), stage 1, circuit 1
1
312 SCP, stage 1, circuit 1
1
313 Number of starts, stage 2, circuit 1
If P4 = 2
1
314 Runtime (in hours), stage 2, circuit 1
If P4 = 2
1
315 SCP, stage 2, circuit 1
If P4 = 2
1
322 No. of water line frost protection cut-offs, circuit 1
1
323 No. of refrigerant line frost protection cut-offs, circuit 1
If P2 ≠ 3
1
324.1
No. of cut-offs caused by discharge
temperature 1 in 24 hours
1
324.2 No. of cut-offs caused by discharge
temperature 2 in 24 hours
If P4 = 2