42
Circuit 1 information:
Circuit 1 High Pressure value:
Value of calculated High Pressure control setpoint:
Circuit 1 condensing temperature value resulting from the previous pressure level and the refrigerant selected:
Stage 1, circuit 1 discharge temperature value:
Stage 2, circuit 1 discharge temperature value:
Desuperheat temperature on discharge 1 (= discharge temperature
– condensation dew point temperature)
Desuperheat temperature on discharge 2 (= discharge temperature
– condensation dew point temperature)
Circuit 1 Low Pressure value:
Circuit 1 evaporating temperature value resulting from the previous pressure value and the refrigerant selected:
Circuit 1 suction temperature value:
Circuit 1 superheat temperature:
Number of cut-offs caused by a High Pressure fault on circuit 1 in 24 hours:
Number of cut-offs caused by a Low Pressure fault on circuit 1 in 24 hours:
P 3 0 0
H P 1 P R E S S U R E
x x . x b
P 3 0 0 . 1
H P 1 C O N T R O L
S E T P O I N T x x . x b
P 3 0 1
C I R C U I T 1
C O N D . T E M P . x x . x °
P 3 0 2 . 1
D I S C H A R G E
T E M P E R A T U R E 1 x x x °
P 3 0 2 . 2
D I S C H A R G E
T E M P E R A T U R E 2 x x x °
P 3 0 3 . 1
D I S C H A R G E 1
D E S U P E R H E A T x x . x °
P 3 0 3 . 2
D I S C H A R G E 2
D E S U P E R H E A T x x . x °
P 3 0 4
L P 1 P R E S S U R E
x x . x b
P 3 0 5
C I R C U I T 1
E V A P . T E M P . x x x . x °
P 3 0 6
C I R C U I T 1
S U C T I O N T E M P . x x x . x °
P 3 0 7
C I R C U I T 1
S U P E R H E A T x x x . x °
P 3 0 8
N O . H P 1 C U T S
I N 2 4 H O U R S x
P 3 0 9
N O . L P 1 C U T S
I N 2 4 H O U R S x