37
Differential used to shut off these heating elements:
Minimum air temperature for operation in heating mode:
Maximum air temperature for operation in cooling mode:
Maximum air temperature for operation in heating mode
Minimum air temperature for operation in cooling mode
Air temperature at which the electric auxiliary heaters or boiler may be turned on:
Authorisation for compressor stages to turn on:
Authorisation for electric stages to turn on:
Electronic expansion valve:
P 2 2 2
O U T . T E M P . D I F F .
W I N T E R P R O T E C . - x x . x °
P 2 2 5
M I N . A I R T E M P . I N
H E A T I N G M O D E - x x °
P 2 2 5 . 1
M A X . A I R T E M P . I N
C O O L I N G M O D E - x x °
P 2 2 5 . 2
M A X . A I R
T E M P . I N H E A T I N G - x x °
P 2 2 5 . 3
M I N . A I R
T E M P . I N C O O L I N G - x x °
P 2 2 6
O U T . T E M P .
A U X I L . A U T H . O N - x x °
P 2 3 0
S T A G E 1 C I R C U I T 1
O N Y E S
P 2 3 1
S T A G E 2 C I R C U I T 1
O N Y E S
P 2 3 2
S T A G E 1 C I R C U I T 2
O N Y E S
P 2 3 3
S T A G E 2 C I R C U I T 2
O N Y E S
P 2 3 5
E L E C T R I C S T A G E 1
O N Y E S
P 2 3 6
E L E C T R I C S T A G E 2
O N Y E S
P 2 3 7
E L E C T R I C S T A G E 3
O N Y E S
P 2 3 8
E L E C T R I C S T A G E 4
O N Y E S
P 6 0 1
C I R C U I T 1
V A L V E T Y P E E X 4
P 6 0 2
C I R C U I T 1
S U P E R H E A T S T P 6 ° C
P 6 0 3
C I R C U I T 1
M O P P O I N T Y E S
Same when „No‟
Same when „No‟