93
26.2 Definition of the programming stages
Setting:
Starting time
Ending time
Selected days (M.T.W.T.F.S.S.)
Type of regulation: Setting 1
– Stop/Setting 2 – Stop/setting 1 – setting 2 / setting 2 – setting 1/non valid.
Setting by fault:
Starting hour: 0h00
Ending hour: 0h00
Validated days: none
Type of regulation not validated.
26.3 Definition of holiday zones
Settings:
Type of zone: non valid, stop, running on setting 1, running on setting 2.
Starting date dd-mm
Ending date dd-mm
Setting by fault Non valid, from 01-01 to 01-01
26.4 Operation
When putting under voltage or when setting the time, the information on the machine status are updated as a function of the programming settings.
The user can change the status of his unit (Run/Stop
– ½ setting regulation) but if a time range or a holiday zone is active, the information will
be updated at the starting or ending time of the programming
In the case where at least one time range or one holiday zone is validated, the parameter P120 is forced on « 2 per console or BMS » and
cannot be modified.
When going under test mode, the programming becomes non active. When leaving the test mode, the unit status information are updated as a
function of the programming settings.
In case of range overlapping, the running mode has priority over the stop mode and setting 1 over setting 2.
Same thing in case of overlapping of zones.
If a programme stage is active (# non validated) and the real day is selected, the status of the unit is as follows:
Type of programme
Status before starting time
Status before starting time
and ending time
Status after ending time
CSG1 -stop
Stop
Running on setting 1
Stop
CSG2 -stop
Stop
Running on setting 2
Stop
CSG1-CSG2
Running on setting 2
Running on setting 1
Running on setting 2
CSG2-CSG1
Running on setting 1
Running on setting 2
Running on setting 1
If at least one time range or one holiday zone is validated, alternate the message machine stopped or setting/temp with a message
in order to signal to the user that the status will be updated on next status change of time range. Display of each of these messages
for 3 seconds.
Message to be displayed:
Access principle:
Through menu 9: "9 PROGRAMMING"
-If validated by key "ENTER", 2 sub-menus "HOURLY PROGRAMMING" and "HOLIDAY ZONES" appear.
Through keys
+
and
–
, select one of the 2 sub- menus, then validate with "ENTER"
Position of the cursor:
When surfing in the various menus, the cursor is located at the top, on the left.
For modifying the settings, it is located at the bottom right side, last but one character.
- When entering the « TIME RANGE » menu "
Display:
Unroll the time range with key
+
or
–
then validate with key "ENTER"
Once the time range has been selected, the regulation type has to be chosen..
By pressing "Enter", we have access to the setting. By pressing key
+
or
–
, the following menus appear. For validation,
press "Enter".
T I M E P R O G R A M M I N G O N
9 - P R O G R A M M I N G
T I M E T A B L E
D A Y S O F F
T I M E T A B L E N ° x
↑
↓
2nd line display:
type of regulation
N° of selected spacing,
from 1 to 6
Содержание Magister 2 Series