18
No.
Description
Setting
Default
Display conditions
Circuit 1 (
CONTINUED
)
1
325 Opening of circuit 1 expansion valve
%
If P42 = CIAT and P3 = 1
1
326 Circuit 1 liquid temperature
°C
If P2 = 1 or 2 or (3 + cooling mode)
1
327 Circuit 1 subcooling
°C
If P2 = 1 or 2 or (3 + cooling mode)
1
328
No. of cut-offs caused by C1 electronic
expansion valve fault in 24 hours
If P42 = ALCO
Circuit 2
1
330 Circuit 2 HP
If P3 = 2
1
330.1 Circuit 2 HP control setpoint
If P3 = 2 and
≠
Intertwined
1
331 Circuit 2 condensation temperature
See appendix
If P3 = 2
1
332.1
Discharge temperature 3
Discharge temperature 2
°C
If P3 = 2 and P4 = 2
If P3 = 2 and P4 = 1
1
332.2 Discharge temperature 4
°C
If P3 = 2 and P5 = 2
1
333.1
Desuperheat on discharge 3
Desuperheat on discharge 2
P332.1 - P331
If P3 = 2 and P4 = 2
If P3 = 2 and P4 = 1
1
333.2 Desuperheat on discharge 4
P332.2 - P331
If P3 = 2 and P5 = 2
1
334 Circuit 2 LP
If P3 = 2
1
335 Circuit 2 evaporation temperature
See appendix
If P3 = 2
1
336 Circuit 2 suction temperature
°C
If P3 = 2
1
337 Circuit 2 superheat
°C
If P3 = 2
1
338 Number of HP2 cut-offs in 24 hours
If P3 = 2
1
339 Number of LP2 cut-offs in 24 hours
If P3 = 2
1
340 Number of starts, stage 1, circuit 2
If P3 = 2
1
341 Runtime (in hours), stage 1, circuit 2
If P3 = 2
1
342 SCP, stage 1, circuit 2
If P3 = 2
1
343 Number of starts, stage 2, circuit 2
If P3 = 2, P5 = 2
1
344 Runtime (in hours), stage 2, circuit 2
If P3 = 2, P5 = 2
1
345 SCP, stage 2, circuit 2
If P3 = 2, P5 = 2
1
352 No. of water line frost protection cut-offs, circuit 2
If P3 = 2 and P2 ≠ 4, 5
1
353 No. of refrigerant line frost protection cut-offs, circuit 2
1
354.1 No. of cut-offs caused by discharge T° 2 in 24 hours
No. of cut-offs caused by discharge T° 3 in 24 hours
If P3 = 2 and P4 = 1
If P3 = 2 and P4 = 2
1
354.2 No. of cut-offs caused by discharge T° 4 in 24 hours
If P3 = 2 and P5 = 2
1
355 Opening of circuit 2 expansion valve
%
P42 = CIAT and P3 = 2
1
356 Circuit 2 liquid temperature
°C
If [P2 = 1 or 2 or (3 + cooling mode)]
and P3 = 2
1
357 Circuit 2 subcooling
°C
If [P2 = 1 or 2 or (3 + cooling mode)]
and P3 = 2
1
358
No. of cut-offs caused by C1 electronic
expansion valve fault in 24 hours
If P42 = ALCO
I
NPUTS
1
400 Automatic machine operation control
Open/Closed
1
402 Setpoint 1/Setpoint 2 selection
Open/Closed
If P120 = 2 via On/Off control
1
403 Water flow check
Open/Closed
1
404 Fan fault check
Open/Closed
If P2 ≠ 1 or 5
1
405 Cooling/Heating input check
Open/Closed
If P119 = Cooling/Heating via On/Off control
1
406 Phase controller
Open/Closed
1
407 Recovery operating mode selection
Open/Closed
If P29 = Yes
1
408 Check of fault input for auxiliary electric heater 1 Open/Closed
If P22 = Yes
1
409 Check of fault input for auxiliary electric heater 2 Open/Closed
If P22 = Yes
1
410 Check of configurable auxiliary electric heater input Open/Closed
If P22 = Yes
1
414 Check of override/load shedding input 1
Open/Closed
1
415 Check of override/load shedding input 2
Open/Closed
If P4 = 2
1
416 Check of override/load shedding input 3
Open/Closed
If P3 = 2
1
417 Check of override/load shedding input 4
Open/Closed
If P5 = 2