SVF-MN Series Frequency Inverter Operation Manual Chapter 5 Function Parameter Detail
110
This parameter is used to set the allowed automatic reset times
when fault occurs to the inverter, fault automatic reset time interval
is decided by P77. When P72 is set to 00 or actual fault reset times
exceed P72 set value, automatic reset function will not be executed
after fault, and it is in fault protection state, reset by hand until fault
is removed. When fault automatic reset is achieved, the inverter
would restart in rotate speed track restart mode when restart
executing again.
P73
Nearest 1st time exception record
0
~
24 0
P74
Nearest 2nd time exception record
P75
Nearest 3rd time exception record
P73
~
P75 function list:
Set
value
Function
Set
value
Function
E000 No
fault
E014 Retain
E001 IGBT short
circuit protect
E015 IPM
fault
E004 Acceleration
over-current
E016 IGBT
module
overheat
fault
E005 Deceleration
over-current
E017 External
fault
E006 Constant
speed
over-current
E018 Retain
E007 Accelerate
overvoltage
E019
Current detection fault or
outputted fault loss fault