SVF-MN Series Frequency Inverter Operation Manual Chapter 5 Function Parameter Detail
104
P55 Slip compensation gain
0.00
~
1.50 0.30
When the inverter drive asynchronous motor, the load increase, slip
frequency would increase, this parameter could compensate rotate
speed, reduce slip frequency, and make the running speed could
approach asynchronous speed when the motor is in rated current.
This parameter is only valid for VF control.
P56
Drive rated voltage
indication
Read-only
Model related
P57
Drive rated current
indication
Read-only
Model related
This parameter set is used to display rated voltage and rated current
of the drive respectively.
P58
Motor overload
ratio
50
~
120%(motor rated
current)
100
It is used to set motor overload ratio, protection is based on P52
motor rated current and this parameter.
P59
Pendulous freq. run mode setting
0
~
2 0
Pendulous freq. run function run mode is set by this parameter.
0
:
Pendulous freq. function close
Pendulous freq. is invalid.
1
:
Pendulous freq. function valid
When the inverter get run command, it could run According to
pendulous freq. preset frequency P62, when it gets stipulated time
P63, it is switched to pendulous freq. run mode.
2
:
Pendulous freq. function condition valid