SVF-MN Series Frequency Inverter Operation Manual Chapter 5 Function Parameter Detail
134
reverse is valid, P60 is set to max freq. P161 is set to 0 frequency.
P163
Current upon recent fault
A
○
P164
Voltage upon recent fault
V
○
P165 Frequency
upon
recent
fault HZ
○
P166
Temperature upon recent
fault
℃
○
P167
Keyboard
potentiometer
direction
0
:
Keyboard potentiometer
cannot change the direction
1
:
Keyboard potentiometer
changes the direction when the
value is less than P160
×
0
:
Direction cannot be changed
1: Direction change can be permission
Note
:
It is only for keyboard access control, and it is valid just when
the frequency is set by the keyboard potentiometer.
When the actual voltage of keyboard potentiometer is less than
P160
,
it is reverse running direction
,
if you turn the potentiometer
left
,
reverse running frequency increases
;
When the actual voltage of keyboard potentiometer is more than
P160
,
it is forward running direction
,
if you turn the potentiometer
right
,
forward running frequency increases;
P171
Water lack protection frequency
30.00Hz
~
50.00Hz
50.00Hz
P172
Water lack current percentage set up
10%
~
100%
50%
P173
Water lack judging delay time
2
~
6000s 10s
P174
Water lack stand-by time
0
~
100mins
30mins
NOTE
:
(1) P171 Water shortage protection frequency, when the running