SVF-MN Series Frequency Inverter Operation Manual Chapter 6 Communication Protocol
137
All the data is expressed by 16 systems.
6.3.2 Salve machine address
The address of frequency inverter should be set through P88, 0 is
broadcast address, slave address could be set to 1~247.
6.3.3 Read function code
Function code 03: present reading the variant the function code.
Realized function
:
reading frequency inverter operation situation,
monitoring parameters, fault information, function code
,
could read 6
continuous address frequency inverter parameter once time.
(1)Readable parameter address scatter
:
Function Address
Data and meaning
BIT5: 0 Standard status,
1 fault status
BIT11: 0 forward
running stats, 1 reverse
running status
BIT12: 0 stop, 1
running
Operation
status
2101H
BIT13: JOP commend
2102H
Setting frequency
0.01HZ
2103H
Output frequency
0.01HZ
2104H
Output current 0.1A
Monitoring
parameters
2105H
DC bus voltage 0.1V