4. Construction Information
Hearths
The appliance does not require a hearth if the flame or any incandescent surface is more than
225mm above any floor covering or 300mm with no floor covering.
Any lower than this a hearth conforming to national regulations is required.
Emissions Exit Connection Types
The minimum chimney height is 2 meters from the spigot.
A smoke pellet can be used to test the flue for effectiveness of the draw, light the smoke pellet
and place to the base of the chimney / liner. Check other parts of the dwelling (including loft
areas) for leakage, down draught etc. If the smoke is drawn into the chimney / liner without
problem, continue with the installation.
If there is little or no flow into the chimney preheat the chimney and repeat the smoke test. If
there are still issues with the draw seek expert advice.
NOTE
– The smoke test gives a fair idea on the draw, but is no guarantee that the products of
combustion from the appliance will clear. A spillage test is also required after the installation.
If spillage occurs after installation a flue liner may be required.
Conventional Class 1 Chimney
Fig. 12
Fig. 13
IMPORTANT NOTE -
If the appliance has been installed in a conventional Class 1 chimney with no liner the
debris shield must be used (see fig. 12) and the warning label (supplied in the manual)
must be fixed to the back of the data plate. (see fig.13)