18.12 Add AlfaPilot functionality
NOTE:
AlfaPilot was formerly named AlfaStoreB.
The AquaEfficiency can work as an AlfaPilot by adding:
•
Valve #2: control valve
•
Pt1: temperature sensor
•
Pt2: surface temperature sensor
•
S5: Outdoor temp sensor (optional)
18.9 Change or add an extra sensor
Following parameter settings must be done to get the AlfaPilot functionality, see the
Parameter
Factory
Default
Setting
Optional setting
Description
S5 Active heating
0
0 Disables /
1 Enables heat curve
Set to1, to be able to use outdoor
sensor S5
Renewable Config
3
0
2=if just added PT1
You get AlfaStore A (AA) (also called
AlfaPilot On/Off)
3=if added both Pt1 and Pt2
You get a AlfaPilot (AP)
AlfaPilot Inverted
1
0
1= application AlfaPilot
SP distrib
0
0/1
Set to 1 if an External setpoint for
Modbus is used (for Pt2 only)
18.12.1 AlfaStore A (AlfaPilot on/off)
This function requires:
•
Valve #2: control valve
•
Pt1: temperature sensor
When DT(Pt1-S3)> DTrecov_min), the function is activated and opens wide the second control valve wired on
AO4 output, extra actuator.
All other AquaEfficiency functions operational.
AlfaStoreA mode is activated in the
DTrecov_Min (default 5°C) is set in
Description
Connection on I/O terminal
No
Marked
24VAC, 22VA max
65
24VAC
0-10 VDC
66
AO4
0V
67
0V
Sensor
Description
Connection on I/O terminal
0V
Pt1-Pt2
Pt1
Primary vessel, temperature sensor, Pt1000, 2 wires
34
35