Installation, service and operating instruction
48
12.4 Operating hours
Operating hours for the following parameters can be checked:
•
Cmd_Distant
•
Triac_Output
•
Therm_Protec_P1/P2/P3/P4
•
AFF_leg_active
•
Cmd_P1/P2/P3/P4
•
Multi_P
•
ECO
•
SAFETY_FCT
•
Booster
•
Tank load
•
High_Temp_Alarm
•
ThTr_Activated
•
Main_Alarm
For more information and description see
1.
Press
key to access to Service Menu, then click on “Continue”.
2.
Select “Operating Hours” in the menu.
The first time you enter this menu, the list is empty.
3.
To add a variable to trend; choose
.
4.
Mark one variable to follow and press the wheel.
5.
Validate the variable by clicking in the Operating Hours box. If this box
is empty the variable is in the list but it is not recorded.
When you go back in the menu (
key), you can see the list with “Cmd_P1”
parameter, and on the right side, the operating hours.
For more details, click on the line to open the sub-menu.
Here you can read that P1 has been operating less than 1 hour, has been
switched one time and status is On.
Proceed the same way to add extra variables.