11.4 S1 Menu Secondary Outlet
S1 is the master sensor.
Parameter
Factory
Default
Setting
Optional setting
Description
SP_T_Sec_Outlet
60°C
DHW Setpoint
Change setpoint value in clock program
Delta T S1 HiAlm
10°C
0-50
High Temperature Alarm if Ts1 >
SP_T_SecDelta Ts1 HiAlm
High T Alarm Delay
1 min
0-30
High temp alarm is effective after this
temporisation
High Alarm Auto Reset
0
0/1
0=MANUAL alarm clear
1=AUTO alarm clear
High_Alm_Reset
Off
Off/On
Put ON to clear an high temp alarm,
then put Off
P_Band AquaFirst
40
0<P<200°C
P to be less reactive
(-200 to 200)
Negative values
in cooling
P to be more reactive (be careful of
"pumping" effect)
I_Time AquaFirst
15
0-200 sec
P to be less reactive
P to be more reactive (be careful of
"pumping" effect)
D_Time AquaFirst
2 sec
0-200sec
P_Band AquaEff
80
0<P<200°C
P to be less reactive
(-200 to 200)
Negative values
in cooling
P to be more reactive (be careful of
"pumping" effect)
I_Time_AquaEff
15
0-200 sec
P to be less reactive
P to be more reactive (be careful of
"pumping" effect)
D_Time_AquaEff
2 sec
0-200sec
11.5 Sensor 2 menu, secondary inlet temperature sensor
When the temperature measured with S1 and S2 suddenly increases or decreases, this function will send an
action signal to the control valve and the primary pump.
The Delta T (S1-S2) function is only valid for variable charging pumps.
When the S2 temperature approaches S1 temperature, an auxiliary control loop reduces charging pump speed
down to a minimum of settable value (see below), at the opposite, if the temperature on S2 decreases, the
pump speed increases.