CHARGING WITH THE TIMER
GB
(GB) 4
GB
On starting charging, the ammeter on the battery charger will indicate a high current
value (generally towards full scale) which will slowly go down until reaching a very
low value (0.5 - 2A).
This value depends on the battery’s capacity and condition.
✓
When the battery is fully charged, the electrolyte will be near boiling point.
✓
It is advisable to stop charging at this point so as not to overheat the elements,
and to prevent oxidation of the plates. In this way you can keep the battery in good
condition.
✓
Ensure you select the appropriate charging current. Excess charging current can
cause serious damage to batteries.
✓
Generally, it is best to select a charging current corresponding to 1/10 of the bat-
tery’s capacity (Ah); initially, you can select a current slightly above this value.
The currents available while starting up are as follows:
5.0 CHARGING WITH THE TIMER
WARNING:
with the timer in position “0”, the charge position are
off. In order to use the charges in the “traditional” manner, place
the timer in the “NORMAL CHARGING” position. All charging
position also function with the timer (up to 60’).
6.0 STARTING OF AN ENGINE
The starting of a vehicule by booster is necessary any time that the battery does
not have enough power to feed the starter. In this case the energy needed can be
supplied by the booster in starting mode.
Make the connections as described at Para.
1.2
:
VERSION 500A
a.
Set the switch (Ref.
2
- Fig. 1 page 3) on “
START
”.
b.
Start engine normally.
c.
At started engine, turn off battery charger setting the switch (Ref.
1
- Fig.
1 page 3)
on
“OFF”
.
VERSION 650A and 1250A
a.
Set the switch (Ref.
3
- Fig. 2 page 3) on
“Stand-by - START”
.
b.
Start engine normally and in same time turn ON the booster by the button
“START”
(Ref.
4
- Fig. 2 page 3) or by the remote control (Fig.
A
- pag.
4).
c.
At started engine, release the button
“START”
(Ref.
4
- Fig. 2 page 3)
d.
Disconnect the cable by the battery in the following sequence: NEGATIV -
POSITIV.
e.
Turn OFF the battery charger by the switch in position (Ref.
3
- Fig. 2 page
3) “0”.
POS.
MEAN
CURRENT (A)
NOMINAL
CAPACITY (Ah)
VERSION
500 A
12V
MIN 1
14
125
MIN 2
16
165
MAX 1
19
240
MAX 2
24
325
24V
MIN 1
14
120
MIN 2
17
170
MAX 1
19
240
MAX 2
24
345
VERSION
650 A
12V
1
11
90
2
12
120
3
16
160
4
19
190
5
22
260
6
26
330
24V
1
13
110
2
16
140
3
20
200
4
23
260
5
26
320
6
30
390
Fig.A
VERSION
1250 A
12V
1
40
380
2
42
430
3
46
530
4
52
590
5
63
730
6
66
840
7
70
950
24V
1
30
310
2
33
350
3
35
380
4
40
410
5
50
590
6
56
680
7
62
760
POS.
MEAN
CURRENT (A)
NOMINAL
CAPACITY (Ah)